background image

INSTALLATION (CONTINUED)

 

 

INSTALLING THE VENTING SYSTEM 

 

These models of wall furnaces are designed for direct venting through a wall.  
Only venting components specifically approved for these furnaces may be used.   
The flow of combustion gases and ventilation air must not be obstructed.   
Minimum clearance between pipes and combustible materials is one (1) inch (25.4 mm). 

 

Vent terminal must be 18.0” away from an adjacent wall. 
Minimum clearance between vent cap and combustible material 1 ¾”. 
 
IMPORTANT: The appliance’s venting system should be inspected at least once a year and immediately cleaned if 
necessary. 
 

IMPORTANT:  THE VENT-AIR INTAKE SYSTEM MUST BE PROPERLY INSTALLED TO INSURE PROPER AND 
SAFE OPERATION.  THE VENT-AIR INTAKE SYSTEM MUST ALSO BE PROPERLY RE-INSTALLED AND RE-
SEALED TO INSURE PROPER AND SAFE OPERATION.   

 

Warning:

 Failure to position the parts in accordance with these diagrams or failure to use only parts specifically 

approved with this appliance may result in property damage or personal injury. 

Avertissement:

 Risque de dommages ou de blessures si les pièces ne sont pas installées conform´ment à ces 

schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées. 

 

CAUTION: ALL JOINTS MUST BE AIR-TIGHT. 

 

The venting system consists of: one injected-aluminum cap (A), one vent pipe (B), one vent-air intake pipe (C), one rod 
(D), one nut (E), one outdoor mounting plate (F) and one silicon-rubber ring (G). (See figure 14). 

 

 

 

                                        Figure 14                                                                          Figure 15

 

 

1.  Measure thickness of the wall as shown in figure 15. 
2.  If pipes (B), (C) and the rod are long, trim them according to thickness of the wall, as shown in the following table. 

 

 

3.  The hole at the outside of the wall must be a square of 11 ½” (290 mm) x 11 ½” (290 mm). (See figure 17). 
4.  From the outside of the wall, screw the rod slightly onto support located inside the appliance flue outlet. 
5.  Slide pipes (B) and (C) through the hole in the wall, and connect them to the appliance flue outlet and air intake, 

respectively. 

6.  The outdoor mounting plate and the silicon-rubber ring should be installed between the vent cap and the exterior 

wall. The plate must be positioned flush to the wall and with its standoffs inserted into the wall and sealed with a 
non-hardening mastic (silicone caulk). (See figure 17). 
Position the outdoor mounting plate so that the vent-air intake pipe has a slight downward slope to the outside. 

The 

downward slope is necessary to prevent the entry of rainwater.

 

 

vent pipe (B) 

vent-air intake pipe (C) 

Rod (D) 

TABLE 3 

Lengths of pipes and rod. 

wall thickness  

+ 3 3/8“ (86 mm) 

wall thickness  

+ 2 1/2“ (64 mm) 

wall thickness  

+ 5 7/8“ (149.5 mm) 

Содержание DVEL 12

Страница 1: ...SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne touchez aucun interrupteur Ne pas vous servir des t l phones dans le b timent o vous vous trouvez Appelez imm diatement votre fou...

Страница 2: ...personal injury or loss of life Refer to this manual Installation and service must be performed by a qualified installer service agency or the gas supplier Do not use this appliance if any part has b...

Страница 3: ...tion at elevation above 2000 feet 609 9 m manufactured to specified deration conditions for Canada and the United States NOTE Minimum Gas Inlet Pressure for purpose of input adjustment The efficiency...

Страница 4: ...ff valve n Ground joint union n Test gauge connection n Sediment trap n Tee joint n Pipe wrench The installation location shall provide the following a adequate combustion and ventilation air and b ad...

Страница 5: ...in a horizontal distance of 2 feet 61 cm from the center line of the terminal D 12 inches 30 cm 1 2 M Clearance to unventilated soffit E Clearance to outside corner F Clearance to inside corner G To e...

Страница 6: ...and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room as the appliance Clothing or other flammable material should not...

Страница 7: ...HE HANGING BRACKET ON A WOODEN WALL 1 Taking into account the minimum clearances mentioned in figure 4 locate the closest wall stud which will serve to hold the appliance and mark the hole center at a...

Страница 8: ...ging bracket and drill the four holes 6 Insert in each hole the anchors provided 7 Place back the hanging bracket and fix it with four screws MOUNTING THE HEATER ON HANGING BRACKET Place the heater on...

Страница 9: ...ppareil sont utilis es CAUTION ALL JOINTS MUST BE AIR TIGHT The venting system consists of one injected aluminum cap A one vent pipe B one vent air intake pipe C one rod D one nut E one outdoor mounti...

Страница 10: ...nsor from any damage during shipping or while handling it before it is definitely installed the thermostat sensor has not been attached to its final location in the appliance So once the heater is ins...

Страница 11: ...uge connections upstream of the gas supply connection to the heater Figure 21 WARNING For L P Gas use PRESSURE REGULATED gas supply Do not directly connect LP supply tank to the pressure regulator on...

Страница 12: ...excess of psi 3 5 kPa The appliance must be isolated from the gas supply piping system by closing equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures...

Страница 13: ...12 OPERATION CONTINUED Pilot Burner...

Страница 14: ...13 POUR COUPER L ADMISION DE GAZ DE L APPAREIL Veilleuse ALLUMAGE...

Страница 15: ...from the manufacturing process It is recommended to burn a new wall furnace for at least two 2 hours the first time that it is used CLEANING AND MAINTENANCE WARNING Turn off heater and let cool before...

Страница 16: ...attern top view Models DVEL 8 and 12 SECONDARY FLAME PRIMARY FLAME THERMOCOUPLE PILOT FLAME Fig 26 Correct main burner flame pattern top view Model DVEL 20 Cleaning the Main Burner Orifice and Main Bu...

Страница 17: ...hen installed 4 Continue holding down control knob Repeat igniting operation until air is removed 5 Pilot is clogged 5 Clean pilot orifice or replace pilot assembly When ignitor button is pressed ther...

Страница 18: ...ses 1 Problem will stop after a while of operation 1 Turning control knob to HI position when burner is cold 1 Turn control knob to LO position and let warm up for a minute 2 Air in gas line 2 Operate...

Страница 19: ...ements parts must be returned the authorized distributor A UNDER WARRANTY Contact authorized dealers of this product If they are unable to supply original replacement part s call the authorized distri...

Страница 20: ...19 Model DVEL 8 19...

Страница 21: ...Model DVEL 12 20...

Страница 22: ...Model DVEL 20 21...

Страница 23: ...Sensor bracket 18 05078 Knob support 19 01021307 Elbow 3 8 NPT x 3 8 NPT 20 01021301 Elbow 1 4 BSP x 1 4 BSP 21 05083 05228 05334 Bracket 22 01082001 01081403 02230113 01082102 01082002 01081403 Burne...

Страница 24: ...5 05137 05257 05376 Top Radiation Shield 46 01160902 Nipple 1 4 BSP x 3 8 NPT 47 02830110B 02830138B 02830140 Burner tubing 48 02830109B 02830137B 02830141B Pilot tubing 49 011935A Nut 50 01024001 028...

Страница 25: ...24 ESKABE S A Ruta 2 No 323 7600 Mar del Plata Pcia de Buenos Aires Argentina Authorized Distributor in USA and Canada Cod Mat XXXX XX XXX...

Отзывы: