rev. 00 of 01-09-10 / pg. 4

__________________________________________________________________________________________ 

Please note that the in terms of measuring the level of CO

2

, the detector will reach maximum precision after 

14 days of uninterrupted operation of the device following installation or a long period of stoppage (several 

months). 

Still, acceptable precision is achieved after two days of operation, in other words after the first full calibration 

cycled according to the ABC Logic™ self-calibration system algorithm. 

In order to obtain maximum precision, during the calibration period following installation (or long period of 

stoppage) do not expose the detector to high quantities of CO2, for example the ongoing presence of many 

people in the premises where the detector is installed. 

Use a permanent marker to write the replacement date of the detector on the plate provided and place it in a 

visible position (after installation is completed). 

Use a wet cloth and mild detergent to periodically clean the device. 

Do not use aggressive detergents like alcohol, ammonia, solvents etc. 

Before cleaning the detector, switch off the system power supply to avoid the risk of electric shock. 

Warning

 

The detector and its sensing element have been designed for ongoing use in areas where there is permanent 

occupation by people, so normally pollution-free. 

The presence of gases or vapours from some aggressive substances such as alcohol, silicons or solvents 

found in some detergents or polishes, or from the fumes generated by cooking or also an excess of steam, 

may cause inappropriate action of the detector and in the long term could affect the reliability of the device. 

__________________________________________________________________________________________ 

__________________________________________________________________________________________ 

__________________________________________________________________________________________ 

Technical 
specifications

 

Power supply (see models) 

230Vac 

±

10% or 115Vac 

±

 10% or 24Vac/dc

±

 10% 

Frequency / Consumption 

50/60Hz / 3.5W maximum, 2.5W average 

Sensing element 

    

CO

2

 

 

  

Temperature 

 

  Relative humidity 

• 

NDIR (nondispersive infrared) 

• 

NTC thermistor 

• 

Capacitive sensor series HS 

Measuring range 

    

CO

2

 

 

  

Temperature 

 

  

Relative humidity 

• 

0...20.000ppm (other ranges on request) 

• 

0…50°C 

• 

0...99% RH 

Measuring precision (@25°C) 

    

CO

2

 

 

  

Temperature 

 

  

Relative humidity 

• 

±

3% of the readout 

• 

±

3% 

• 

±

10% 

Measuring stability  

   

(CO

2

2% on full scale, for the lifetime of the sensor 

Measuring linearity  

   

(CO

2

1% of full scale 

Dependance on altitude  

   

(CO

2

0.13% of the readout per mm of Mercury column 

Calibration for altitude 

   

(CO

2

0…9.900m at steps of 100m 

Dependance on temperature  

   

(CO

2

0.2% of full scale 

Calibration for temperature 

   

(CO

2

) Automatic 

Response time (T90) 

   

(CO

2

) 2m 

Command outputs (see models) 

• 

SPDT relay - capacity of the contact 250Vac 3A or 30Vdc 
3A 

• 

Analogue 4...20mA or 0…10Vdc 

Alarm threshold 

Settable from interface with operator 

Operational lifetime of a detector 

15 years from installation 

Max detectable area  

about  100m

2

 (approximate; for larger areas install several 

devices at suitable distances from each other) 

Protection Rating 

IP40 when correctly installed 

Operating temperature / humidity 
Storage temperature / humidity 

0...50°C / 0...95% RH (non condensing) 
- 40...70°C / 0...95% RH (non condensing) 

Dimensions and weight 

Mounting holes compatible with 503 type flush mounting box 
Maximum dimensions: 130 x 90 x 40 mm 
Weight: 360g 

Enclosure 

ABS/PC UL94-V0 flame retardant 

Conformity 

 

EMC Electromagnetic Compatibility

 

Low Voltage (LVD) 

 

EMC 2004/108/EC – EN 61000-6-1 + EN 61000-6-3

 

LV 2006/95/EC – EN60730-1 

To be filled in by Installer

 

Installer's stamp

 

Installation site 

Product order number 

Installation date 

Replacement date 

 