EsiWelma s.r.l.

 

rev. 00 of 01-09-10 / pg. 3

__________________________________________________________________________________________ 

Electrical Installation

 

Make sure the wiring conforms to the standards in 
force.

 

The devices must be connected to the mains power 
supply and remain permanently powered.

 

Omnipolar disconnection must be included in the 
mains. 

Some possible wiring diagrams: 

Example a):  

- Command of an audible alarm from a 

detection point. 

Example b):  

- Command of a visual alarm from 

several detection points.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operator interface

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Commissioning 

Power-up the detector by holding the (power) button pressed for about 2 seconds and check that the display 

shows the measurements in the format as above. 

To select the threshold set-points and the set-points for all the other parameters, first press the selection 

(switch) and then the (up) and (down) buttons to set the value for each one. 

The set-points can only be changed if its value is flashing; to rapidly increase the set-points, hold the (down) 

or (up) button pressed for more than 3 seconds. 

After selecting and changing the set-points and any other parameters, lock them in so they are not 

accidentally changed by pressing the (down) and (up) buttons together and holding them down for more than 

5 seconds; the set-points are locked in when the display shows this symbol  . 

To restore the possibility of changing set-points, once more press down on the (down) and (up) buttons at the 

same time; the set-points can be changed when the display no longer shows this symbol  . 

Carry out an operational test using  a CO

2

 gas canister with dosage valve; release a small amount of gas 

close to the grille below and control the correct engagement of the command and/or alarm device connected 

to the relay as well as the appearance on the display of the symbol 

It is advisable to repeat the operational test at least once a year, or after a prolonged period of stoppage. 

If other test methods are used instead of the one described the detector may generate different, unexpected 

responses. In particular, the use of inappropriate substances or vapours (alcohol or silicon-based solvents 

etc.) or in any case, high concentrations of test gases could cause permanent damage to the sensing element 

and may cause the detector to operate incorrectly. 

The detector needs no periodic maintenance, with the exception of the periodic operational test and its repla-

cement 15 years after the installation date. 

__________________________________________________________________________________________ 

230Vac  or  115Vac  or 24Vac/dc

 

a)

1 (L)

 

2 (N)

 

ESN.F.D..

 

7 (C)

6 (NO) 

230Vac  or  115Vac  or 24Vac/dc

b)

 

1 (L)

2 (N)

ESN.F.D..

 

7 (C)

6 (NO) 

1 (L)

2 (N)

ESN.F.D..

 

7 (C)

6 (NO) 

Power

 On/Off 

 

Do

wn

 

(D

ecr

ease)

 

 

Up

 

(I

ncr

ease)

 

 

Sel

e

ct 

(S

wit

c

h

Humidity 

Temperature

 

Lock Set 

point data

 

Status  

of relay

 

Carbon Dioxide

 

Отзывы: