11220 V1.0_R1.1 Manual 8-Fold Switch Module 

Page 1 of 6 

Art. No. 11220 V2 

 

User Guide

 

8-Fold Switch Module with Button Inputs

 

for 1-Wire Bus

 

 

 

 

  8 power relays with 8 A continuous power

 

  Control inputs for button and 1-Wire Bus

 

  LED indicator for activated relays

 

  Switching of direct power consumers or 

alternative power consumers, e.g. lighting, 
heating or sockets

 

  Top-hat rail cases for switchboard assembly

 

  Easy software-based control

 

  Low space requirement in switchboard

 

  Easy to assemble

 

 

 

  

 

Introduction 

Before you start assembling the 

8-fold Switch Module

 and put the device into operation, please read this 

assembly and operating instructions carefully to the end, especially the section referring to the safety notes. 
 

Product description 

With the 

8-Fold Switch Module 

it is possible to connect direct power consumers and alternative power consumers 

with an output of up to 8A continuous power.  
The switch module can be controlled directly by an external button (e.g. light switch) or by button-menu on the 
module top side, independent of the 1-Wire interface For switch operation only 12 V power is required. Thus, a 
high reliability, e.g. for switching of lightings, outlet circuits or other consumers can be reached, even in case of a 
breakdown of a central control / software. 
 
To operate the switch module we recommend the use of one of our 1-Wire Hub modules. 

 

Technical data 

Switching channels: 

8, changeover relay (NO contact)

 

Switching voltage: 

Maximally 250V direct power voltage or alternative power voltage

 

Switching power/Power: 

Maximum 8A continuous power per output

 and maximally 1840VA continuous power 

in case of Ohm resistive load. 
Minimum load 10mA  

Maximum 10A power in total for all outputs

 

 

 

In case of capacitive or inductive loads, appropriate additional wirings, e.g. spark 
suppressor capacitors must be considered. Maximum power and output will be reduced. 

Fuses:   

External preliminary fuse with 10A recommended

 

Data interface:   

1-Wire Bus (12V, data and load)

 

1-Wire Component: 

DS2408 (8-Fold I/O)

 

Supply voltage:   

12VDC (+/-10 %)

 