Art. No. 11322 
 

 

 

User Guide 

1-Wire Hub III DC 

 

 

  Central power supply for 1-Wire

i

 Network and all 

ESERA Modules 

  18 

– 36 VDC power supply (adapted to PLC 

typical 24 VDC) 

  Filtered power supplies for trouble-free bus 

supply 

  Top-hat rail case for switchboard assembly 

  Top-hat rail case, width 71 mm 

  Monitoring of output voltages and currents via 

1-Wire module 

  Screw-based connection 

  Easy to assemble 

  Energy efficient design with high efficiency 

 
 
 
 
 

Introduction 

Before you start assembling the 

1-Wire Hub III DC

 and before you take the device into operation, please 

read this assembly and operating instruction carefully to the end, especially the section referring to the safety 
notes. 
 

Product description 

The 

1-Wire Hub III DC

 serves as the central power supply within a 1-Wire network. The 1-Wire Hub III DC is 

providing the required bus voltage (5 V / 12 V) and also distributes the 1-Wire data line. The 1-Wire Hub III DC is 
normally required only once in a network and is connected directly to a 1-Wire Bus Coupler or 1-Wire Controller. 
Due to the input voltage range of 18 

– 36 V, the device is ideally adapted to the system environment of PLC 

controls, for 24 VDC supply. 
To operate the 1-Wire Hub III, an upstream system power supply, providing the input voltage of 24 V, e.g. a DIN 
rail power supply, is necessary. 
 
The 1-Wire Hub III DC is equipped with a measuring function for the output voltage and current of the 5 V and 12 
V output by default. This is measured by an integrated 1-Wire module (DS2450). Due to voltage- and current 
measurements, issues with the supply of a 1-Wire network, such as overload or short circuit, may be detected at 
an early stage. 
The 1-Wire Hub III DC is designed for a broad supply range of 18 

– 36 VDC (nominal 24 VDC). 

 

As an "emergency power supply" for a 1-Wire network, the 5 V input voltage is provided in only one direction to 
the output, even when there is no 24 V supply voltage available. This is to ensure a minimum function of the 
1-Wire network, even in the event of failure of the 24 V main supply. In this operating mode the 12 V voltage is 
not available. 
Output power of the 1-Wire Hub III DC is designed to hold up to 40 modules. 
 

 

8 devices of 1-Wire air quality sensors (11127) and 8 devices of 1-Wire 8-way switch modules (11220 (8x8A) or 6 
devices of 11228 (8x16A)) can be connected. 
The device is designed for DIN top-hat rail mounting in a switchboard. 

Содержание 1-Wire Hub III DC

Страница 1: ...e in a network and is connected directly to a 1 Wire Bus Coupler or 1 Wire Controller Due to the input voltage range of 18 36 V the device is ideally adapted to the system environment of PLC controls for 24 VDC supply To operate the 1 Wire Hub III an upstream system power supply providing the input voltage of 24 V e g a DIN rail power supply is necessary The 1 Wire Hub III DC is equipped with a me...

Страница 2: ...age 12V 12 Bit 5 V Port 2 current 5V 12 Bit 5 V Port 3 voltage 5V 12 Bit 5 V Input voltage typ 24 V DC 18 36 V DC Energy Efficiency 90 Output Power max 15W Output 5 V maximum 0 5 A 12 V maximum 1 A in total for 5 V and 12 V maximum 15W Indicator Power LED 5 V and 1 Wire activity Interfaces Input for 1 Wire Controller or 1 Wire Bus Coupler Output for 3 x 1 Wire network output 1 adjacent top hat rai...

Страница 3: ... V mA DS2450_Port2 20 current 12 V mA DS2450_Port0 22 9 Connection plan A connection plan and a connection example with further modules are available in our webshop Pin assignment input power supply Bus Coupler Controller 14 plus supply voltage 15 minus supply voltage 16 grounding PE 23 Ground 1 Wire input 24 1 Wire data line 25 5 V input from master e g 1 Wire Controller or 1 Wire Bus Coupler Pin...

Страница 4: ... requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11322 V2 0 R1 1 Manual Page 4 of 6 10 Connection Example Example with 1 Wire Controller or 1 Wire Gateway 1 Wire Hub III Dual Digital Output and 8 fold digital input ...

Страница 5: ...ischarged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the device must be immediately taken out of operation until the faulty cable has been replaced When using components or modules it is absolutely necessary to comply with the requirements set out in the accompanying descripti...

Страница 6: ...SERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We are constantly developing our products further and reserve the right to make changes and improvements to any of the products described in this documentation without prior notice Should you require documents or information on older versio...

Отзывы: