9.2.
DATA PRINT ON/OFF
Setting of the operating mode for data output of the sensor data
Selectable states: ON = 1 / OFF = 0
OFF = 0 => Data output in one line with one CR, ON = 1 => Continuous output in one line with separator "|".
Factory setting: ON = 1
Command
: SET,SYS,DATAPRINT,0 or 1
9.3.
DATA TIME 0, 10 - 240
Setting of the cycle time for sending 1-Wire / OWD data
Selectable range: 0; 10 - 240
0 = Data only on request, cycle time = 10 - 240 seconds
Factory setting: 10
Command
: SET,SYS,DATATIME,0 or 10 - 240
9.4.
OWB POLLTIME 1 - 240 (data output, available starting with firmware V1.15_51)
Here you can set the poll time for all 1-Wire devices. The time (in seconds) defines, how often the 1-Wire devices
are queried.
Selectable range: Poll time (cycle time) = 1 - 240 seconds.
Note: A poll time faster than 2 seconds should only be selected for a small number of max. 5 or 6 1-Wire devices.
Note: The DATA TIME cannot be selected shorter than the OWB POLLTIME.
(DATA TIME>= POLLTIME).
Factory setting: Poll time is 2 seconds
Command
: SET,SYS,POLLTIME,1 - 240
9.5.
OWB SEARCH ON/OFF
Different methods of searching for OWDs and sorting them into the OWD list can be selected.
Selectable states: ON = 1 or 2, OFF = 0
Details to the two search functions can be found in the programming manual under the tab "DOKU".
0=no search, 1=complete cyclic search (sequence of blocks may change)
2=adaptive cyclic search for new blocks. New blocks are written to the first free space in the OWD list.
Factory setting: ON = 2
Note: With "OWB SEARCH 1" the OWD numbers may be re-sorted.
Command
: SET,OWB,SEARCHTIME,0 - 2
9.6.
OWB SEARCH TIME 10 - 240
Setting of the cycle time for the search function
Selectable range: 10 - 240
Factory setting: 10 seconds,
Command
: SET,OWB,SEARCHTIME,10 - 240