Connector Assignment
6.3 24V
DANGER
The CAN-AIR/2 must be supplied by a limited current source (see chapter 5.1)!
DANGER
Device of protection class III
The CAN-AIR/2 may only be driven by power supply current circuits, that are contact
protected. A power supply, that provides a safety extra-low voltage (SELV or PELV)
according to EN 60950-1, complies with this conditions.
Functional earthing is allowed, but must not conflict with the safety considerations of the
system.
Device connector:
Phoenix Contact MC 1,5/2-G-3,81
Plug component:
Phoenix Contact FK-MCP 1,5-3,81 with spring-cage connection
Pin Position:
Pin Assignment:
Pin
1
2
Labelling of
CAN-AIR/2
P
M
Signal
P24
(+ 24 V)
M24
(GND)
Signal Description:
P24...
24V-power supply voltage, typical 24VDC (min. 8V, max. 32V)
M24...
reference potential
NOTICE
Please note the correct polarity!
INFORMATION
I
n the CAN-AIR/2-PoC (esd-order No:
C.2067.06) version the 24 V power supply voltage
can also be applied via the DSUB9 connector. See chapter: “Power-over-CAN (CAN-
AIR2-PoC only) “ on page 39.
Page 38 of 53
Hardware Manual • Doc. No.: C.2067.21 / Rev. 1.5