GD350A series high-performance multifunction VFD
-236-
Function
code
Name
Description
Default Modify
P21.29
Speed feedforward
filter time constant
(pulse string speed
mode)
It is the filter time constant detected by pulse
string when the speed reference source is set
to pulse string (when P00.06=12 or
P00.07=12
Setting range: 0–3200.0ms
10.0ms
○
P21.30
Numerator of the
2nd command ratio
1–65535
1000
○
P21.31
Pulse-given speed
measure method
0: Main control board
1: PG card
2: Hybrid
0
○
P21.32
Reserved
0–65535
0
○
P21.33
Set value of
clearing encoder
count
0–65535
0
○
P22 group––Spindle positioning
P22.00
Spindle positioning
mode selection
Bit0: Enable spindle positioning
0: Disable
1: Enable
Bit1: Select spindle positioning reference point
0: Z pulse input
1: S2/S3/S4 terminal input
Bit2: Search for reference point
0: Search the reference point only once
1: Search the reference point every time
Bit3: Enable reference point calibration
0: Disable
1: Enable
Bit4: Positioning mode selection 1
0: Set direction positioning
1: Near-by direction positioning
Bit5: Positioning mode selection 2
0: Forward positioning
1: Reverse positioning
Bit6: Zeroing command selection
0: Electric level mode
1: Pulse mode
Bit7: Reference point calibration mode
0
○