![Esco invt GD350A Series Скачать руководство пользователя страница 161](http://html1.mh-extra.com/html/esco/invt-gd350a-series/invt-gd350a-series_product-manual_2426081161.webp)
GD350A series high-performance multifunction VFD
-156-
Function
code
Name
Description
Default Modify
11:
EtherCat/Profinet/EthernetIP
communication
12: Programmable expansion card
P03.12
Torque set through
keypad
-300.0%–300.0% (of the motor rated current)
20.0%
○
P03.13
Torque reference
filter time
0.000–10.000s
0.010s
○
P03.14
Setting source of
forward rotation
upper-limit
frequency in torque
control
0: Keypad (P03.16)
1: AI1 (100% corresponding to the max.
frequency)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Multi-step setting (same as the above)
6: Modbus/Modbus TCP
communication(same as the above)
7: Profibus/CANopen/DeviceNet
communication (same as the above)
8: Ethernet communication (same as the
above)
9: Pulse frequency HDIB (same as the above)
10: EtherCat/Profinet/EthernetIP
communication
11: Programmable expansion card
12: Reserved
0
○
P03.15
Setting source of
reverse rotation
upper-limit
frequency in torque
control
0: Keypad (P03.17)
1: AI1 (100% corresponding to the max.
frequency)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Multi-step setting (same as the above)
6: Modbus/Modbus TCP communication
(same as the above)
7: Profibus/CANopen/DeviceNet
communication (same as the above)
8: Ethernet communication (same as the
above)
0
○