8.5.
Programming level of serial interface P-04
The pa ra me ters of the pro gram ming level P-04 exists anly by pa nel me ters with the
op ti on se ri al in ter face. The in ter face mo duls are bi di rec tio nal and works at the sla ve
mode.
Param.
Description
Setting range
Default
values
4-00
Interface address
0 .. 31
1
4-01
Interface baud rate
0 ->
: 300 baud
1 ->
: 600 baud
2 ->
: 1200 baud
3 ->
: 2400 baud
4 ->
: 4800 baud
5 ->
: 9600 baud
6 ->
: 19200 aud
0 .. 6
6
4-02
Transmission-Mode
0 ->
PC-Mode
1 ->
Terminal-Mode timer controlled
2 ->
Terminal-Mode button/input
controlled
0 .. 2
0
4-03
Sendrate in sec.
0 ->
permanent transmission
0 .. 3600
0
4-04
Data source for serial interface
0 ->
Value of encoder
1 ->
MAX value
2 ->
MIN value
3 ->
Hold value
0 .. 3
0
4End
Leave programming level P-04
The pa nel me ter can be con trol led com pletly with the se ri al in ter face. That me ans the
pa nel me ter can in itia li zed of a host (unit name, re vi si on num ber). It can be ad just all
pa ra me ters and it can be read all mea su red va lues resp. all va lues of the pa ra me ters.
8.5.1. Transmission-Mode
PC- Mo de
In PC- Mo de a sin gle trans mis si on is star ted with a spe cial com mand from the PC. A
com ple te list of all pos si ble com mands is available as ad di tio nal ma nu al.