8 Configuring the Recorder
8-20
TESLA LITE User Manual
D03283R01.10
Description
Optional field (12 characters). Provides an additional description of
the channel that forms part of the channel name. Should always be
used with External Input channels to uniquely name the channel.
(“Channel Grouping and Naming” on page 8-7).
Channel
Identifies the physical External Input used by this channel. This
number is identified on the rear of the TESLA LITE chassis. The list
only shows inputs which have not been assigned to other channels.
To get an overview of channel assignments, switch to the Channel
Tree view and look at the External Channel list.
Trigger Settings
Definite Delay
Specifies how long the trigger condition must be present before a trig-
ger is declared. Settable from 0 to 5,000 ms in eighth cycle incre-
ments.
The delay setting is in addition to the pickup delay imposed by the
input “glitch” filtering, which is approximately 700 microseconds.
Label
Text to designate the active and inactive states. Default is "on" and
"off". Maximum 8 characters.
Trigger Actions
Enable
Enables or disables the associated trigger. A trigger can be disabled
without altering the rest of its settings.
Fault
Initiates a fault (high speed) recording when triggered.
Swing
Initiates a swing (low speed) recording when triggered.
If both Fault and Swing are enabled, the recorder will attempt to cre-
ate a combined record.
Log
Logs a message in the Event Log when triggered.
Notify
Contacts the RecordBase Central Station when triggered. Can be
used to initiate wide area swing recordings and/or automated record
transfer (“Notify” on page 7-13).
Cross Trigger
OC #6 is Cross Trigger, OC #7 is Recorder Functional
Priority
Specifies the priority to be assigned to records created by this trigger.
The priority is used to determine Central Station notification.
1 - 3 (3 is the highest priority). (“Notify” on page 7-13).
Alarm Contact
Specifies a rear panel contact to be closed when triggered. Contacts
are closed momentarily for one second. Contact assignment is not
exclusive, allowing multiple triggers to activate the same contact.
Contacts assigned for storage alarms (“TESLA Alarms” on page 8-6)
will not be available for use here.
Table 8.9: External Input Channel Settings
Содержание tesla lite
Страница 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 20: ......
Страница 24: ......
Страница 78: ......
Страница 126: ......
Страница 134: ......
Страница 214: ......
Страница 234: ......
Страница 280: ......
Страница 282: ...Appendix G TESLA LITE Drawings Appendix G 2 TESLA LITE User Manual D03283R01 10 Figure H 1 Mechanical Drawings 401 450 ...
Страница 284: ......
Страница 288: ......