5 Offliner Settings Software
D02416R04.00
F-PRO 5100 User Manual
5-13
Setting Groups
Figure 5.13: Setting Groups Comments
The relay has eight setting groups (1 to 8). You can change all relay setting pa-
rameters except the physical connections such as input or output parameters in
each setting group. Use any one of the 16 available Group Logic Statements
per setting group to perform Setting Group changes. The Group Logic state-
ments are similar to the ProLogic statements with the following exceptions, the
sole function is to activate one of the eight setting groups and the processing is
in a slower half second cycle. Group Logic inputs statements can be driven
from ProLogic, any external input, previous Group Logic statements or virtual
inputs. Each Group Logic statement includes five inputs (with Boolean state-
ments), one latch state and one pickup delay timer. View the active setting
group from the Terminal Mode, from the front panel or from a record stored by
the relay (the active setting group is stored with the record).
Feeder Parameters
Figure 5.14: Feeder Parameters
Feeder Parameters
Line
Line to Line Voltage
Fixed (from System Parameters)