background image

 

 

DINLINE ALARM RELAY (DAR)

 

 

INSTALLATION INSTRUCTIONS

 

www.erico.com 

 

Page 1 of 2 

  

 

 

 

                    

 

 

1.  PREPARATION 

DANGER

:  Electrical shock or burn hazard. 

Installation of this device should only be made 
by qualified personnel. Failure to lockout 

electrical power during installation or maintenance can 
result in fatal electrocution or severe burns. Before 
making any connections be sure that power has been 
removed from all associated wiring, electrical panels, 
and other electrical equipment. 

 
 
CAUTION NOTES

:  

1.  The installation of this device should follow all 

applicable electrical codes, such as the National 
Electrical Code. 

2.  Check to make sure line voltage does not exceed 

DAR275V voltage ratings. 

3.  Follow all instructions to ensure correct and safe 

operation.  

4.  Do not attempt to open or tamper with the DAR in 

any way as this may compromise performance and 
will void warranty. No user serviceable parts are 
contained. 

2.  INTRODUCTION

 

Selected  DSD,  TDS  &  TDF  DINLINE  Surge  Protection 

Devices include status monitoring circuits which provide visual 

status display of device capacity. They may also provide a low 

voltage opto-coupler alarm output circuit that can be connect to 

the  DAR  to  provide  potential  free  (Form  C)  change-over 

contacts.  The  DAR  alarm  contacts  may  be  used  to  provide 

output to external alarm systems or remote monitoring circuits. 
One DAR can be used per DSD/TDS/TDF opto-coupler alarm 

or  up  to  16  DSD  opto-coupler  alarms  can  be  connected  in 

series  to  the  one  DAR  to  provide  a  common  output.  It  is 

recommended  that  the  DAR  be  powered  from  the  same 

power  circuit  that  feeds  the  device(s)  being  monitored, 

however  the  DAR  can  be  powered  from  other  circuits.  This 

allows for example, one DAR unit to be connected to separate 

SPDs that are protecting a three phase circuit. 
 

Note. Depending upon the usage of the DAR output contacts, 

failure of power to the DAR may be interpreted as a failure of 

one or more of the SPDs being monitored. Visual inspection 

of the DAR and SPDs status displays would determine this. 

3.  MOUNTING

 

The  DAR  is  designed  to  clip  to  35mm  (top  hat)  DIN  rails 

(standard  EN50022).  Unless  otherwise  mechanically 

restrained,  use  horizontal  DIN  rails  with  the  DAR  module 

spring clips to the bottom and the label text the correct way up. 

NOTE:

 The DAR must be installed in an enclosure or panel 

that: 

  prevents the DAR temperature from exceeding  

 

131°F (55°C) 

•  provides adequate electrical and safety protection 

•  prevents the ingress of moisture and water 

•    allows DAR status indicators to be inspected 

 

4.  ELECTRICAL CONNECTION

  

The interconnecting wiring should: 

• 

be  of  size  #10  to #14 AWG (2.5mm² to 6mm²) solid or 

stranded conductor.  

• 

The wire insulation should be stripped back 5/16" (8mm).   

• 

NOTE:  Do  not  use  greater  than  9inlbs  (1Nm)  of  torque 

when tightening the terminals.  

CONNECTION TO TELECOMMUNICATIONS NETWORKS 

The  DAR  is  approved  for  use  in  Australia  where  the  alarm 

contacts may be connected to private lines or building cabling 

associated  with  the  telecommunications  network.  NO  direct 

connection to the public switched network should be made. 

 

 

MODEL NUMBER 

DAR 275V

 

PRV Switchboard Manual Section 2 - Terasaki Circuit Breakers Installation Instructions Vendor Manual

Q-Pulse Id: VM78

12/11/2012

Page 1 of 2

Отзывы: