2
3000044983
English
Read the instructions carefully
before installation and commis-
sioning!
Leave the instructions for users/
customers for future reference!
Our updated product documen-
tation can be accessed at
www.erco.com/download.
General safety information
Warning!
Risk of electric shock!
Before carrying out maintenance and
installation on the luminaire, disconnect
from the mains supply and also from
any other DALI control wiring, and
ensure that all power is switched off.
Attention!
- Do not open the luminaire head. In
case of damage or a defective LED
module, the entire luminaire must be
returned to the factory.
- Do not operate luminaires with
damaged or missing safety glass.
- When installing, always observe the
national installation and accident pre-
vention regulations.
Intended use
The luminaire is suitable for outdoor
and indoor use and is approved for a
height of light source exceeding 15m.
Dimensions (D), max. reference plane
for wind loads (A) and weight (W) are
detailed in Fig. 5.
Choosing the mounting location
Position the luminaire so as to avoid
operation in direct sunlight or near
other sources of heat. High ambient
temperatures can reduce the life and
efficiency of the control gear or LED
module.
Electrical installation
For 3-circuit installation: to avoid any
damage to the control gear, the neutral
conductor must never be connected or
disconnected during operation.
Overvoltage protection
ERCO uses electronic control gear with
overvoltage protection in accordance
with DIN EN 61547. If additional protec-
tion from spikes is required, e.g. when
switching off inductive loads, separate
overvoltage protection units should be
installed.
Luminaire with DALI control gear
- All cables, materials and devices used
must be suitable for mains voltage, as
the DALI signal is not transmitted using
safety extra low voltage (SELV).
- For general information on DALI,
please go to: www.dali-ag.org.
Notes on corrosion protection
Ensure that the powder coating is not
damaged during installation or mainte-
nance work. Any damage, which becomes
wet, can result in corrosion occurring. In
aggressive environments, the installation
and maintenance of all parts will require
the appropriate protective measures. Che-
micals damage the corrosion protection.
Mounting
1. Detach the mounting plate from the
luminaire. Remove the connector bet-
ween luminaire and mounting plate.
2. Drill fixing holes (Fig. 1/2).
3. Insert the connection cable into the
mounting plate. Refer to Fig. 3.
4. Attach the mounting plate diagonally
using 2 heavy load rawl bolts M8 accor-
ding to the manufacturer’s instructions.
Attention! Always select fittings in com-
pliance with the national regulations and
standards applicable to the installation
site. Ensure suitable corrosion resistance
as required for the environment.
5. Make the electric connection. Con-
nect the earth conductor to the moun-
ting plate.
6. Reattach the connector.
7. Fit the luminaire to the mounting
plate and push towards the fixing screw
(Fig. 4). Tighten the fixing screw.
Flashing of the LED module
It is normal for the LED module to flicker
when switching on and off.
Dimming
Depending on the model, the luminaire
can be dimmed using a suitable dimmer
(trailing edge) or via DALI.
Trailing-edge dimmers
Follow the manufacturer’s installation
instructions. For some products, the
luminaire can only be switched on in the
upper dimming range. Before installation
and connection, check luminaire, control
gear and dimmer combination for proper
functioning of the dimmer, especially
when using universal dimmers.
The use of dimmers which are unsuit able
for LED drivers can damage the lumi-
naire, control gear and/or the dimmer.
No responsibility is accepted for the
use of dimmers that are unsuitable for
the luminaire.
Cleaning
Always clean carefully using a soft
cloth and a commercially available,
ph-neutral, alcohol-free, non-abrasive
cleaning agent.
Take care not to damage the powder-
coating.
Cleaning the safety glass
Safety glass can be cleaned with clea-
ning agents that are also suitable for
glass-ceramic cooking hobs.
Disposal
In accordance with EU Directive
WEEE (Waste Electrical and Electro-
nic Equipment), luminaires must not
be disposed of with other household
waste. At the end of their life, lumi-
naires must be taken to the appropriate
local facility available for the disposal
or recycling of electronic products.