Page 26
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
www.eps-germany.de
PSI 10000 4U Serie
1.9.6
The control panel (HMI)
The HMI (
H
uman
M
achine
I
nterface) consists of a display with touchscreen, two rotary knobs, a pushbutton and
an USB port.
1.9.6.1
Touchscreen display
The graphic touchscreen display is divided into a number of areas. The complete display is touch sensitive and
can be operated by finger or stylus to control the equipment.
In normal operation the left hand side is used to show actual values and set values and the right hand side is used
to display status information:
Actual voltage display
Voltage set value input
Actual current display
Current set value input
Actual power display
Power set value input
Additional status
Status area
Touch area for
rotary knob assignment
DC output status
Touch areas MENU
and SETTINGS
Quick menu
Touch areas may be enabled or disabled:
Black text = Enabled
Grey text = Touch area temporarily
disabled
This applies to all touch areas. Some can additionally show a small padlock sign, indicating that
the feature is permanently locked, usually due to a specific setting.
•
Actual / set values area (left hand side)
In normal operation the DC output values (large numbers) and set values (small numbers) for voltage, current
and power are displayed. Resistance set value of the simulated, variable internal resistance is only displayed with
active resistance mode.
When the DC output is switched on the actual regulation mode is displayed as
CV, CC, CP
or
CR
,
next to the
corresponding actual values, as shown in the figure above.
The set values can be adjusted with the rotary knobs next to the display screen or can be entered directly via the
touchscreen. When adjusting with the knobs, pushing the knob will select the digit to be changed. Logically, the
values are increased by clockwise turning and decreased by anti-clockwise rotation.
General display and setting ranges:
Display
Unit
Range
Description
Actual voltage
V
0-125% U
Nom
Actual values of DC output voltage
Set value of voltage
(1
V
0-102% U
Nom
Set value for limiting the DC output voltage
Actual current
A
0.2-125% I
Nom
Actual value of DC output current
Set value of current
(1
A
0-102% I
Nom
Set value for limiting the DC output current
Actual power
W, kW
0-125% P
Nom
Actual value of output power, P = U * I
Set value of power
(1
W, kW
0-102% P
Nom
Set value for limiting DC output power
Set value of internal resistance
(1
Ω
0-100% R
Max
Set value for the simulated internal resistance
Adjustment limits
ditto
0-102% nom U-max, I-min etc., related to the physical values
Protection settings
ditto
0-110% nom
OVP, OCP etc., related to the physical values
(1