ENWARE TOUCH FREE WALL SENSOR TAP 

- ON/OFF DEMAND SENSOR

Installation and Maintenance Instructions

I00314_Dec19

EMW803A-150 

On / Off Demand Stainless Steel Wall Sensor Panel 
With 150mm Spout

EMW803A-200

On / Off Demand Stainless Steel Wall Sensor Panel 
With 200mm Spout

EMW803A-LO

On / Off Demand Stainless Steel Wall Sensor 
Panel Only

Содержание EMW803A-150

Страница 1: ...com au ENWARE TOUCH FREE WALL SENSOR TAP ON OFF DEMAND SENSOR Installation and Maintenance Instructions I00314_Dec19 EMW803A 150 On Off Demand Stainless Steel Wall Sensor Panel With 150mm Spout EMW80...

Страница 2: ...me out and close the valve automatically This is intended to conserve water and prevent overflows COMPONENTS The wall sensor tap kit comes standard with a fixed aerated spout a 1 2 solenoid valve a se...

Страница 3: ...and AS NZS 3500 may void the product and performance warranty provisions Reference should also be made to the Australasian Health Facility Guidelines AHFG ABCB and Local Government regulations when c...

Страница 4: ...in possible range of the sensor can trigger the sensor randomly or constantly turn it on PASSING TRAFFIC Be sure that passing traffic cannot trigger the sensor Allow at least 400mm clearance between s...

Страница 5: ...must be installed in such a way that they can be easily removed and replaced if necessary It is recommended that all cabling is fed through 20mm conduit to allow for servicing and replacement in futu...

Страница 6: ...01 Note If flexible connectors are used they must be made accessible for future servicing or replacement installation ISOLATION VALVE AND MESH STRAINER NOT SUPPLIED UNION TYPE CONNECTION UNION TYPE C...

Страница 7: ...he solenoid body must align with the direction of water flow SEE IMAGE 02 The black casing for solenoid can be turned around to suit the direction of wiring connection by first loosening the hex nut o...

Страница 8: ...tor Cable Connect spade connectors to two bottom terminals on solenoid Do not connect to earth terminal on top SEE IMAGE 07 WARNING Protecting from Water Spray Note that the power pack and connections...

Страница 9: ...2 BSP male thread on wall Screw on the spout by hand TESTING Turn on the power to the unit and test the unit See Operating Instructions overpage TESTING Turn the water on and check for leaks Connect a...

Страница 10: ...c TO TURN ON Place hand in front of sensor for half a second at a distance of 5 cm Move hand away Water starts to flow TO TURN OFF Place hand in front of sensor for half a second at a distance of 5 cm...

Страница 11: ...does not turn on when hand is placed in front of sensor Red LED does not light up in the sensor lens Power supply is off or transformer is damaged Turn power on or replace transformer Sensor is damag...

Страница 12: ...nsformer or Solenoid 480222 Spout Aerator 8 Lpm Standard M22 1 SP301 Spare Parts to Suit Old Version EMW802 EMW803 EMW804 Pre 2019 PART CODE PART CODE Sensor On Off Demand incl S S plate bracket adapt...

Страница 13: ...solenoid 3 The solenoid can be disassembled and checked for debris or damage to the diaphragm Refer to Servicing the Solenoid instructions below Take note of the location of the components so that it...

Страница 14: ...d Grease can deteriorate over time and cause the solenoid to malfunction 8 Reassemble the plunger with spring into the core tube Check that the spring is reassembled back together inside the core tube...

Страница 15: ...ke note of the installation firstly to determine if additional cable extensions are required additional to the 4 5 metres and secondly to see if cable access is difficult or if the cable is fed throug...

Страница 16: ...damage to buildings other structures or infrastructure and loss or damage during product transit or transportation making a claim To make a claim under this warranty you must notify us in writing with...