Bellwin | Chapter 4 Monitor
37
Device Temp Setup
Device Temp
: Such device temperature.
High Alarm
: Set up the values of high temp alarm. When temp is higher than
you set, the alarm will occur.
Low Alarm
: Set up the values of low temp alarm. When temp is lower than
you set, the alarm will occurred.
Sensor state
: Temperature sensor has 6 states: "Monitor Normal", "Monitor
Alert", "Monitor Off-line, the "Non-monitor Normal" "Non-monitor Alert",
"Non-monitor Off-line".
Monitor Normal:
“Offline Monitor” is checked. And external
temperature is not higher than
“High Alarm” or lower than “Low Alarm”
setting.
Monitor Alert:
“Offline Monitor” is checked. And external temperature
is higher than
“High Alarm” or lower than “Low Alarm” setting.
Move the mouse over the icons for its detailed information, and the menus
are displayed as follows: