MAC 10

®

 LEAC

Fan Filter Unit 

Standard, RSR, & RSRE Models 

INSTALLATION, OPERATION & MAINTENANCE MANUAL

Содержание MAC 10 LEAC

Страница 1: ...ENVIRCO Technical Support 800 884 0002 MAC 10 LEAC Fan Filter Unit Standard RSR RSRE Models INSTALLATION OPERATION MAINTENANCE MANUAL...

Страница 2: ...ations of the MAC 10 4 Warnings 4 Part Numbers 4 Installation 5 Cleaning the Prefilter Foam 6 Cleaning the Prefilter G4 Pleated 6 Service Removal and Replacement of Standard Filters 7 Service Removal...

Страница 3: ...LABEL PN 268177 XXX 150412345 BA AS1CH LISTED 2F82 AIR FILTER E152685 Innovators in clean air technology LEAC SUITABLE FOR COMMERCIAL OR INDUSTRIAL USE ONLY C R R R Company Purchased From ____________...

Страница 4: ...son s in accordance with all applicable codes and standards including fire rated construction B When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities...

Страница 5: ...ceiling and lower onto the gasketed grid If using a flexible grid typically supported with wires the unit must be secured to an overhead structure with eyebolts s hooks and chain or 20 all thread A ro...

Страница 6: ...ter is recommended every twelve months or sooner Step 1 To gain access to the prefilter remove the ceiling panel next to the unit if applicable Step 2 Switch the ON OFF switch to the OFF position Step...

Страница 7: ...ift the lid assembly off the HEPA ULPA filter See Figure 4 Discard the used filter as per requirements of the applicable regulations Carefully install the filter deflectors into the new filter using t...

Страница 8: ...einstalling the removed filter Determine if the gel has lost its ability to seal If so have a certified professional replace the missing dried out and or severely damaged gel Step 5 Place the filter e...

Страница 9: ...crews See Figure 6 Step 8 Using an adjustable wrench loosen the two set screws that attach the blower wheel to the motor shaft Step 9 Mark the location of the motor support bracket belly band then loo...

Страница 10: ...5 Replace with the new motor and reassemble by reversing the above steps Set the location of the motor mount bracket as measured see above Step 6 Set the spacing at 0 25 6 35 mm clearance between the...

Страница 11: ...rical box See Figure 8 Recommended fan speed during initial start up and operation is the LOW speed As airflow eventually decreases due to filter loading fan speed may be increased by moving the rocke...

Страница 12: ...ower supply for proper voltage amperage and distribution frequency Step 4 Replace HEPA filter if the air velocity remains low HIGH AIR VELOCITY Adjust visual speed control for lower blower output NON...

Страница 13: ...o n O p e r a t i o n M a i n t e n a n c e M a n u a l MAC 10 LEAC Fan Filter Unit MAC 10 LEAC Wiring Diagram Figure 9 Wiring Diagram Innovators in Clean Air Technology www envirco com Installation...

Страница 14: ...e filter 20x20 64125 001 All filter part numbers are based on the standard MAC 10 sizes 2x4 23 63x47 63 If the unit in question is not this size or the part number includes a Z contact the factory for...

Страница 15: ...allation operation and maintenance of the Goods and conformance with the proper operation instruction manuals provided by ENVIRCO or its suppliers or subcontractors b Buyer keeping proper records of o...

Страница 16: ...Grid System Hospital Healthcare Hospital Healthcare IsoClean and IsoClean with Ultraviolet Light AirCeil Hospi Gard Room Pressure Monitor Enviramedic Products HOR Horizontal Flow Enclosure HCF Horizo...