EP.HIO WIRING GUIDE

Содержание EP.HIO

Страница 1: ...Copyright Entrypass Corporation ENTRYPASS TECHNICAL WIRING GUIDE Version 1 04 Last Updated 23 06 2016 EP HIO WIRING GUIDE...

Страница 2: ...on 3 support 6 and 10 digits format For existing site P1 will detect its card database to determine 6 or 10 digits For new site user can change the digits as long as the card database is empty Please...

Страница 3: ...ct your system installer Your installer is familiar with your system configuration and should be able to answer any of your questions Should you need additional information please call our Technical S...

Страница 4: ...ase follow the instruction below Observe precautions while handling the circuit board assembly by using proper grounding straps and handling precautions at all Visually ensure no onboard parts is brok...

Страница 5: ...LED Communication LED Digital Input Connecter Digital Output Connecter Digital Output LED Digital Input LED Power Connector Dip switch 32 Bits Processor Power Connector For Daughter Board Expansion Ba...

Страница 6: ...al Output LED Digital Input LED Expansion Board Power Cables Digital Input Connecter Digital Output Connecter With the expansion board attached to the HIO controller the HIO now support 16 Digital Inp...

Страница 7: ...Copyright Entrypass Corporation ENTRYPASS TECHNICAL WIRING GUIDE ENTRYPASS Power Supply Unit Specification Switching Power Supply 12V DC 3 Amp Minimum Power Supply Unit Specification...

Страница 8: ...ontroller C C RS 485 I000 meter Maximum PCC Pc Communicator RS 232 10 meter EntryPass Platform1 Server Access Control System RS232 Power Tx Rx HIO 16 HIO 2 HIO 1 C2 C2 C2 C2 C2 C2 When in RS485 mode a...

Страница 9: ...umber 8 ON 1 3 2 4 5 For HIO number 9 ON 1 3 2 4 5 For HIO number 10 ON 1 3 2 4 5 For HIO number 11 ON 1 3 2 4 5 For HIO number 12 ON 1 3 2 4 5 For HIO number 13 ON 1 3 2 4 5 For HIO number 14 ON 1 3...

Страница 10: ...P address 192 168 1 100 2 Subnet Mask 255 255 255 0 3 Gateway 0 0 0 0 4 Server IP address 192 168 1 254 To change the network setting simply logon to the web server The distance from HIO controller to...

Страница 11: ...N6 GND IN7 IN8 GND GND Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Digital Input Is a dry contact point and the input can be configurable either close trigger or open trigger to su...

Страница 12: ...Board Unit Address 2 HIO with Expansion Board Unit Address 9 RS485 1000 Meter Maximum Terminator L3800 Board The On Board HIO is shipped in package with L3800 Is advisable to connect a resistor 100 O...

Страница 13: ...O number 4 ON 1 3 2 4 5 For HIO number 5 ON 1 3 2 4 5 For HIO number 6 ON 1 3 2 4 5 For HIO number 7 ON 1 3 2 4 5 For HIO number 8 If more than 1 HIO controller is connected to the L1000 controller th...

Страница 14: ...6 CM6 NO6 NC7 CM7 NO7 NC8 CM8 NO8 You can select the HIO output either in normally open state NO or normally close state NC and this HIO output connection is connected to the Lift Controller floor but...

Страница 15: ...connection is connected to the Lift Controller floor button location Thus 1 HIO with expansion board can control up to 16 floors Due to the 16 outputs available 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16...

Страница 16: ...1 Performing Cold Start Steps of performing cold start 1 Please ensure that the jumper is inserted on JP1 1 2 2 Press and Hold COLD switch 3 Press RESET Switch and Release RESET switch 4 Release COLD...

Страница 17: ...1 100 Server IP to 192 168 1 254 and Port to 2020 Performing Factory Default Steps of performing factory default 1 Please ensure that the jumper is inserted on JP1 11 12 2 Press and Hold COLD switch 3...

Страница 18: ...eter Maximum To L1000 HIO 2 HIO 8 C2 C2 C2 C2 C2 C2 100 ohm resistor It is advisable to insert a resistor value of 100 ohm on the last HIO controller for termination purpose if installation involve lo...

Страница 19: ...Distance Description Computer to PC Communicator RS 232 10m 30 ft 22 AWG 2 Pairs Shielded PC Communicator to HIO RS 485 1000m 3000 ft 22 AWG 2 Pairs Shielded Network Switch to HIO Network 100m 300 ft...