Entes SPD-D Скачать руководство пользователя страница 1

Single SPD is enough for all devices inside a terminal. 
SPD should be assembled in a close location where the mains connection of the terminal is established. 
These connections should be done by the possible shortest cables and straight lines. 
A cable lug should be used for terminal connections. 
The cable width should be at least 6 mm2.
Neutral and ground lines must be connected.
Short-circuit current of the fuse before SPD must be minimum 6kA.

Inputs:

L1, L2, L3 : Terminals where phase connections will be established.
N  : Terminal where neutral connection will be established.
E  : Terminal where ground connection will be established.

Troubleshooting:

If, the device blows a fuse, it means its varistors are short-circuited. The device must be removed and 
replaced with a new one, immediately.

 

The system should be started without any protection.