DC AMMETER

DCA-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS
User Manual and Menu Map

Содержание DCA-10

Страница 1: ...A4741 Rev 1 www entes com tr DC AMMETER DCA 10 10A 10C 10S 10CS 11 11A 11C 11S 11CS User Manual and Menu Map...

Страница 2: ...uarantee The device has a 2 year guarantee In case of a malfunction repairs of the device must be done only by the authorised technical service or the guarantee will be void 1 INTRODUCTION 1 1 1 APPLI...

Страница 3: ...tored system current should reside can be determined and a warning signal can be created for the user with Alarm1 C1 and Alarm2 C2 contact outputs if this monitored current goes out of the determined...

Страница 4: ...is 9 Units belonging to measurements and analog output parameters 10 Indicates that the contact or contacts are in a high fault state When entering a value in High Alarm type it lights up continuousl...

Страница 5: ...2 10V 0 4 20 mA Analog Output connector 3 pin V GND I DCA 10A 11A RS 485 connector 4 Pin DCA 10S 10CS 11S 11CS 2 Relay connectors 4 pin DCA 10C 10CS 11C 11CS Supply input 2 pin 85 265V AC DC DCA 10 10...

Страница 6: ...urrent need of your system Example If your current need is 100A the minimum current value of the shunt that you will connect must be 150A If you connect a 100A shunt to a 100A system it may cause the...

Страница 7: ...ling time in this menu Period value can be entered between 1 600 seconds PERIOD PERIOD PERIOD 01 PERIOD SET 001 05 050 SET SET 2 2 3 ALARMS Alarms Menu DCA 10C 10CS 11C 11CS devices have two normally...

Страница 8: ...LRM STAT Alarm Status Setting Menu Alarm function of the relay is activated in this menu If OFF option is selected in this menu alarm parameters of the corresponding relay can t be accessed If the ala...

Страница 9: ...It can be entered between 000 0 and 999 9 seconds H ON DEL 50 0 H ON DEL SET 005 005 0 SET SET 050 0 H ON DEL H ON DEL HIGH ALARM HGH VALUE The highest value that you want the measured current to reac...

Страница 10: ...50 LOW HYS SET 03 030 SET SET 050 LOW HYS LOW HYS A A L ON DEL It is the delay time for the low current alarm to activate The value is entered as seconds It can be entered between 000 0 and 999 9 seco...

Страница 11: ...e current value corresponding to the maximum value of the selected analog output type is set in this menu This value can be entered between Shunt Current values Example When the analog output type is...

Страница 12: ...sub menus ADDRESS BAUDRATE PARITY ADDRESS Address Setting Address information can be entered between 1 and 247 ADDRESS ADDRESS ADDRESS 01 ADDRESS SET 001 03 030 SET SET PARITY BAUDRATE 9600 ADDRESS 00...

Страница 13: ...00 70 77 MODBUS RTU PROTOCOL Standart MODBUS RTU message is shown below T ADDRESS 8 BIT FUNCTION 8 BIT DATA N x 8 BIT CRCH CRCL T Modbus Functions The T times corresponds to a time in which data must...

Страница 14: ...for Buttons section of this user manual NOTE Stored values are not affected from power outages After you select YES option under the value that you want to reset and approve the changes when you exit...

Страница 15: ...y settings are loaded in this menu A 4 digit password is asked when entering this menu If password protection is active the password isn t asked again when entering this menu because it was entered du...

Страница 16: ...Change Password Menu Password is changed in this menu 2 2 11 ESCAPE Exiting Main Menu It is used to exit the main menu If any changes has been made in the menus a confirmation is asked to save those...

Страница 17: ...A 10C 10CS 11C 11CS Only for DCA 10A 11A Only for DCA 10S 10CS 11S 11CS Only for DCA 11 11A 11C 11S 11CS DCA 10 10A 10C 10S 10CS 85 265V AC DC DCA 11 11A 11C 11S 11CS 9 56V DC Control Panel Area Dimen...

Страница 18: ...on Output Inverse Off Alarm Type High Alarm High Alarm Value 100A Low Alarm Value 10A High Alarm Hysteresis 10A Low Alarm Hysteresis 5A 33 34 GND GND B A PC REPEATER MAX 1200 mt MAX 1200 mt TR B A RS...

Страница 19: ...11C 11S 11CS Frequency 50 60 Hz DCA 10 10A 10C 10S 10CS Supply Input Power Consumption 4 VA Measuring Input Power Consumption 1 VA Measuring Input Resistance Rin 1K Iin 150mV Measuring Current Range...

Страница 20: ...ation Type Flush Mounting PR 20 Weight 0 240 kg Installation Class Class III Panel Cutout Dimensions 48X96 mm PR 20 6 REGISTER TABLE Trip Active Latch Inactive Latch Active Description Range W R Unit...

Страница 21: ...N Delay Alarm 1 High Alarm OFF Delay Alarm 2 Latch Function Alarm 2 Trip Function Alarm 1 Low Alarm ON Delay Alarm 1 Low Alarm OFF Delay Alarm 2 Activation Protection Inactive Protection Active Trip A...

Страница 22: ...elay 1 HighAlarm OFF delay doesn t count b4 1 Relay 1 HighAlarm OFF delay counts b5 0 Relay 1 Low Alarm ON delay doesn t count b5 1 Relay 1 Low Alarm ON delay counts b6 0 Relay 1 Low Alarm OFF delay d...

Страница 23: ...OUTPUT TYPE VOLT RANGE 0 10 V 2 OUTPUT TYPE VOLT RANGE 2 10 V 3 OUTPUT TYPE CURRENT RANGE 0 20 mA 4 OUTPUT TYPE CURRENT RANGE 4 20 mA 0 OUTPUT INACTIVE Backlight Status Contrast Average Period Langua...

Страница 24: ...INGLE REGISTER 10H PRESET MULTIPLE REGISTERS 2BH READ DEVICE INFO When a reading operation from addresses that are not present on the device is done 0 zero value will be read When a writing operation...

Страница 25: ...LUE 010 A HIGH HYS 005 A H ON DEL 020 0 HGH VALUE 100 A TRIP NO TRIP TRIP LATCH NO BACK MENU Only valid for DCA 10C 10CS 11C 11CS Selected parameter is displayed Selected parameter is displayed Select...

Страница 26: ...ed PARITY 01 24 ADDRESS Last entered value is displayed Only valid for DCA 10S 10CS 11S 11CS ANLG OUT ANLG OUT 0 20 ANLG OUT mA mA ANLG OUT mA ANLG OUT V ANLG OUT V HIGHEST 100 A LOWEST 000 A BACK MEN...

Страница 27: ...d is active LANGUAGE LANGUAGE ENTR PASS ENTR PASS 000 000 FCTRY SET SETTINGS DONE Selected parameter is displayed RESET RESET MIN RESET MAX BACK MENU RESET MIN RESET MAX DISPLYSET BACKLIGHT CONTRAST B...

Страница 28: ...SS ENTR PASS 000 000 PASS ACTV ENTR PASS Selected parameter is displayed SAVE Changes are saved Changes are discarded 120 00 OLD PASS OLD PASS 000 000 NEW PASS 000 AGAIN 000 AGAIN 111 PAS CHNGD If pas...