© 2019 Enphase Energy Inc.
12
BWM-450MM-A allows 450 mm battery-to-battery spacing:
BWM-600MM-A allows 600 mm battery-to-battery spacing:
3. Install the AC Isolator (if required)
Following all local codes and standards:
a.
Choose an AC Isolator that can break the maximum rated current of the branch circuit under load
(20 A maximum).
b.
Connect one side of the isolator to the switchboard (load centre):
c.
Verify that AC voltage at the site is within range. Single-phase L1 (Active) to N must measure
between 200 and 270 VAC).
WARNING
! Risk of equipment failure. Size the conductor gauge to account for voltage rise
for both the branch circuit and all upstream conductors leading back to the PCC (point of
common coupling). Refer to the technical brief on voltage rise at