ISA-40 Oxygen Monitor

ENMET

 Corporation

1

1.0 Introduction

1.0 Introduction

The 

ISA-40

 system monitors the atmosphere of a work environment where depletion of oxygen can occur.  Air

contains 20.9% oxygen by volume; if oxygen in the air is displaced by a heavy gas, or if a decrease in the oxygen
content of air occurs in a confined area, the atmosphere could become hazardous to human life.

The 

ISA-40

 system employs galvanic micro-fuel cells as oxygen detection transducers.  The output current of each cell

increases or decreases according to the partial pressure of oxygen in the surrounding air, which corresponds to the
oxygen content.  The system monitors the oxygen content continuously, and if the oxygen content at any sensor location
drops to the alarm point (usually 18.0% by volume), the instrument provides audio and visual alarms at the control unit.
An audio alarm also occurs at the sensor location.  Internal relay contacts can be used to activate additional alarm signals
and/or external equipment.  Oxygen content from 16% to 26% by volume is constantly displayed by meters on the
control unit.  The 

ISA-40

 system is an alarm device which minimizes the risk of harm or death to personnel by warning

them of a hazardous oxygen deficient atmosphere with enough time for them to take action.

An 

ISA-40

 system consists of a number of identical channels of oxygen deficiency detection.  Each circuit cell

combination makes up a separate channel. 

ISA-40-2

 has two identical circuits with related oxygen cells; likewise, an

ISA-40-4

 has four channels.  If the cell is enclosed in a remote sensor, each cell can be located in a separate area up to

1000 feet from the instrument enclosure.  The cells are connected to the control unit electrically by wire or cable.  Each
plug-in circuit board contains the circuitry for two channels. 

ISA-40

 instruments described in this manual can contain

up to 4 channels.  This particular manual is for the 

ISA-40-1

 through the 

ISA-40-4

.

N

OTE

:

All specifications stated in this manual may change without notice.

1.1 Unpack

Unpack the 

ISA-40

 and examine it for shipping damage.  If such damage is observed, notify both 

ENMET

 customer service

personnel and the commercial carrier involved immediately.

Regarding Damaged Shipments

N

OTE

:

 It is your responsibility to follow these instructions.  If they are not followed, the carrier will

not honor any claims for damage.

q

 

This shipment was carefully inspected, verified and properly packaged at our company and delivered to the carrier in good condition.

q

 

When it was picked up by the carrier at 

ENMET

, it legally became your company’s property.

q

 

If your shipment arrives damaged:

 

Keep the items, packing material, and carton “As Is.”  Within 5 days of receipt, notify the carrier’s local office and request
immediate inspection of the carton and the contents.

 

After the inspection and after you have received written acknowledgment of the damage from the carrier, contact 

ENMET

 Customer

Service for return authorization and further instructions.  Have your Purchase Order and Sales Order numbers available.

q

 

ENMET

 either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage, usually

$100.00.  Repair or replacement charges above that value are your company’s responsibility.

q

 

The shipping company may offer optional insurance coverage. 

ENMET

 only insures shipments with the shipping company when

asked to do so in writing by our customer.  If you need your shipments insured, please forward a written request to 

ENMET

Customer Service.

Regarding Shortages

If there are any shortages or questions regarding this shipment, please notify 

ENMET

 Customer Service within 5 days of receipt at

the following address:

ENMET Corporation

680 Fairfield Court

Ann Arbor, MI 48108

734-761-1270

734-761-3220 Fax

1.2 Check Order

Check, the contents of the shipment against the purchase order.  Verify that the 

ISA-40

 is received as ordered.  If there are

accessories on the order, verify that they are present.  Check the contents of calibration kits.  Notify 

ENMET

 customer service

personnel of any discrepancy immediately.

1.3 Serial Numbers

Each 

ISA-40

 is serialized.  These numbers are on tags on the equipment and are on record in an 

ENMET

 database.

Содержание ISA-40 Series

Страница 1: ...ENMET ENMET Corporation PO Box 979 Ann Arbor MI 48106 0979 80015 001 12 05 91 MCN 204 01 19 99 MCN 277 07 01 02 ISA 40 ISA 40 Oxygen Monitor Oxygen Monitor Manual ...

Страница 2: ...nt 12 5 4 Circuit Breakers Fuse 14 6 0 ISA 40 SPECIFICATIONS 15 7 0 SERVICE INFORMATION 15 7 1 Replacement Part Numbers 15 7 2 Return for Repair 16 8 0 WARRANTY 17 List of Illustrations FIGURE 1 ISA 40 CONTROL UNIT EXTERIOR 2 FIGURE 2 MOUNTING DIMENSIONS 3 TABLE 1 POWER SUPPLY WIRING 3 FIGURE 3 OXYGEN CELL INSTALLATION 5 TABLE 2 REMOTE SENSOR ASSEMBLY WIRING WITHOUT INTRINSIC SAFETY BARRIER 6 TABL...

Страница 3: ...ange without notice 1 1 Unpack Unpack the ISA 40 and examine it for shipping damage If such damage is observed notify both ENMET customer service personnel and the commercial carrier involved immediately Regarding Damaged Shipments NOTE It is your responsibility to follow these instructions If they are not followed the carrier will not honor any claims for damage q This shipment was carefully insp...

Страница 4: ...e unit is in high alarm Lamp Green When this light is on the unit is operating and is not in alarm When this light is off the unit is in alarm OR power to the unit has been interrupted Switch Audio Alarm Switch to disable audio alarm horn on off Indicator Audio Alarm Light Amber When this light is on the audio alarm is disabled Relay Reset Button Push button to release latching relay Figure 1 ISA ...

Страница 5: ...nting the electronics control unit See Figure 2 for mounting dimensions NOTE All dimensions are given in inches 2 Apply 110 VAC and or 12 VDC power to the appropriate terminals on TB5 and TB3 Refer to the Wiring Information table Both 110 VAC and 12 VDC power can be applied together the 12 VDC is standby power source DC current will flow only when the AC power is interrupted Table 1 Power Supply W...

Страница 6: ...oldering iron 18 gauge or larger insulated wire and 60 tin 40 lead resin sore solder CAUTION This procedure should be performed only by personnel with electrical repair experience 1 Disconnect power from control unit 2 Remove instrument circuit board to access transformer standoffs on motherboard 3 Unscrew the cover retaining screw and rotate protective standoff cover until standoffs are exposed 4...

Страница 7: ...he control unit and remove screws to remove cell circuit board See Figure 1 3 2 Carefully remove the cell from the package 3 Remove the metal shorting clip or spring from cell pins See Figure 3 4 Plug the cell into the component side of the cell circuit board center pin to center hole See Figure 3 Place the board in the enclosure and replace the screws to secure the cell and circuit board 5 Wait a...

Страница 8: ...2 Audio Alarm TB1 2 Horn TBS 2 2 Oxygen Cell TB1 2 O2 TBS 3 2 Oxygen Cell TB1 2 O2 TBS 4 3 Audio Alarm TB4 1 TBS 1 3 Audio Alarm TB2 3 Horn TBS 2 3 Oxygen Cell TB2 3 O2 TBS 3 3 Oxygen Cell TB2 3 O2 TBS 4 4 Audio Alarm TB4 2 TBS 1 4 Audio Alarm TB2 4 Horn TBS 2 4 Oxygen Cell TB2 4 O2 TBS 3 4 Oxygen Cell TB2 4 O2 TBS 4 Table 2A Remote Sensor Assembly Wiring with Intrinsic Safety Barrier Channel Sign...

Страница 9: ...ing Clip or Spring Bottom View O2 Sensor Center Pin Negative Outer Pin Positive O2 Cell Circuit Board w cell installed on circuit side O2 Cell TB4 TB2 TB1 TB3 T B 3 T B 4 T B 2 T B 1 T B 5 TB7 ISA 40 Interior View Optional Intrinsic Safety Barriers Detailed View Intrinsic Safety Barriers Example Channel 1 ISB installed IS1 1 IS1 2 IS1 3 ...

Страница 10: ...ing clip or spring from the cell See Figure 4 8 Plug the cell into the component side of the cell circuit board in the oxygen sensor assembly insert the center pin of the cell into the center hole of the circuit board Place the cell in position in the top of the assembly enclosure and replace the screws to secure the cell in place CAUTION Do not tighten screws too much doing so can damage the comp...

Страница 11: ...junction between the oxygen cell and the sensor connection o the ISA 40 motherboard See the wiring information Table 2A and Figure 4 3 3 Relay Outputs Relay contacts can be used to activate other alarm signals or equipment away from the control unit enclosure when there is an alarm condition and when the AC or DC power is interrupted The contacts supplied are dry with a rating of 2 Amp continuous ...

Страница 12: ... 4 TB4 4COM Common 3 3 2 Latching Relays Latching relays are available on TB7 the terminal strip located on the auxiliary relay circuit assembly located on the upper surface of the control unit enclosure These relays once triggered by an alarm condition remain latched in the alarm position until released by an operator who activates the relay release pushbutton switch on the front of the enclosure...

Страница 13: ... adjust the oxygen cell in an area where an oxygen deficiency may exist Always adjust the oxygen cell in fresh air Use cylinders of 20 9 by volume oxygen in nitrogen if necessary to guarantee oxygen content See Section 7 1 Avoid exposure to toxic gas environments 4 3 Atmospheric Pressure Variations The galvanic oxygen deficiency transducer cell current output is directly proportional to the partia...

Страница 14: ...installing a cell in a remote sensor assembly with audio alarm disconnect the ground side of the sensor assembly audio alarm during this process to avoid spurious alarms while changing the cell reconnect it when done 5 3 Circuit Alignment Each ISA 40 system is aligned at the factory however due to prolonged use oxygen cell replacement and assorted other circumstances it may become necessary to rea...

Страница 15: ...re the oxygen cell is properly connected by measuring the voltage between the cell leads this voltage must be between 0 043 and 0 09 VDC c Measure the Low Level Set voltage for the channel by connecting the voltmeter leads to the appropriate test points shown below Channel Test point On Circuit Board 1 TP101 TP103 For channel s 1 and 2 2 TP201 TP203 For channels 1 and 2 3 TP101 TP103 For channel s...

Страница 16: ...led 20 9 by volume oxygen to the sensor for a couple of minutes then adjust gain e If possible exhale all your breath over the oxygen cell The meter reading should drop and the oxygen alarm should come on at the predetermined alarm point usually 18 0 oxygen by volume f If the oxygen alarm does not come on at this point repeat the entire procedure checking terminal connections test points and volta...

Страница 17: ...Range 32 F to 125 F ENMET Warranty 6 months form shipment Size 1 25 diameter by 0 80 long Weight 26 grams Expected Life Up to 14 months in air NOTE All specifications stated in this manual may change without notice 7 0 Service Information 7 0 Service Information 7 1 Replacement Part Numbers A full set of replacement part numbers and prices are a part of the documentation which accompanied the orde...

Страница 18: ... information can result in processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a minimum 30 evaluation fee even if returned unrepaired Unclaimed instruments that ENMET has received without appropriate paperwork or attempts to advise repair costs that have been un...

Страница 19: ...nt mode ENMET shall not be liable for any loss or damage caused by the improper use of the product The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this equipment This warranty is expressly given in lieu of all other warranties either expressed or implied including that of merchantability and a...