Introduction 

 
The Enica Pulse-Splitter range is designed to split the pulse signal from a utility 
meter to several dataloggers. The device is passive and does not have any moving 
parts or batteries. The splitter can be used with electric, gas, water or in fact any 
meter with a pulse output (Volt-free contact, Reed relay or Open-collector). 
 

For the purposes of gas meter installations, Enica Pulse Splitters could be 
regarded as “Simple Apparatus”, however, the device provides no Intrinsic 
Safety  isolation  via  optical  or  galvanic  barriers  and  the  details  within  this 
instruction  manual  MUST  be  adhered  to.  Only  loggers  with  suitable  Ex 
certification  and  conforming  to  the  electrical  ratings  detailed  in  this 
document should be connected to the Pulse-Splitter when being used in a 
gas meter situation.

 

 
Installation Procedure – Pulse-Splitter 
 
Note: The standard version of the pulse splitter is not waterproof and is not 
suitable for use in wet environments such as water meter pits. 
 

Step 1:

 Open the enclosure. 

 

Step  2:

  Wire  the  pulse  input  (coming  from  the  utility  meter)  to  the 

terminals labelled INPUT. Please observe polarity if applicable. 
 

Step 3:

 Wire the 1st datalogger to Output 1. Please observe polarity 

 and – on the terminal blocks 
 

Step 4:

 Wire the 2

nd

 and 3

rd

 dataloggers to Output 2 and 3 respectively. 

Please observe polarity  and – on the terminal blocks 

 

Step  5:

  Close  the  enclosure  using  the  screws  provided.  Mount  the 

Pulse-Splitter in a suitable location. 

 

 

 

Installation Procedure – Waterproof Pulse Splitter 
 

The waterproof version of the pulse splitter has all internal components 
encapsulated within waterproof gel compound. There are no serviceable parts 
inside and the enclosure should not be opened. 

 

Step 1:

 Wire the pulse input (coming from the utility meter) to IN cable. 

Please  observe  polarity  if  applicable  (White  =  Positive,  Brown  = 
Negative) 
 

Step  2:

  Wire  the  1st  datalogger  to  any  of  the  OUT  cables.  Please 

observe polarity on cable (White = Positive, Brown = Negative) 
 

Step  3:

  Wire  the  2

nd

  and  3

rd

  dataloggers  the  second  and  third  OUT 

cables respectively. Please observe polarity on cable (White = Positive, 
Brown = Negative) 

 
Safety Warnings 
 

 

No user serviceable parts inside.

 

 

Observe the instructions and all warnings on the device and within these 
instructions.

 

 

The installer/end-user is responsible for safe installation.

 

 

Local working practices should be adhered to for installation. 

 

 

The enclosure of the device should be fully fitted.

 

 
 
 
Use of the Device in a Gas/Potentially Explosive Environment 
 

The Enica Pulse Splitter could be regarded as “Simple Apparatus” and could 
therefore be utilised to split meter pulses within a gas meter/potentially explosive 
atmosphere as long as the loggers connected have suitable Ex certification and 
do not exceed the following electrical ratings: 
 
Electrical Ratings for Meter Input 
Ui=0, Ci=0, Li=0 
 
Electrical Ratings for Connected Loggers 
Ui= 7.0V, Li = 14mA, Pi = 20mW, Ci = 0, Li = 0 
Cable length must be a maximum of 10m 
 
“Simple Apparatus" as defined in the European harmonised standards for 
electrical equipment intended for use in potentially explosive atmospheres are 
excluded from the Directive, as they have no own source of ignition. Therefore, 
they do not have to meet the relevant Essential Health and Safety Requirements 
or be subject to the conformity assessment procedures under Directive 94/9/EC.  
 
IMPORTANT: The Pulse-Splitter does not provide any isolation and therefore all 
connected loggers MUST carry suitable Ex Certification.  When used in a gas 
environment, loggers without Ex Certification MUST NOT be connected to the 
pulse splitter without suitable intrinsically safe isolation. 
 

Troubleshooting 

 
In some circumstances, the splitter may show the following symptoms: 
 
Pulses are received by a logger only when a single logger is connected to the 
splitter. When connecting a second or third logger, the pulses are not received 
by any device. In these cases, attempt to ensure pulse wiring makes a true 
circuit through the splitter and back to the meter. 
 
In some other cases, especially if the voltage being applied to the splitter from a 
logging device is low, the splitter can cause a slight volt drop in the logger output 
to the extent where the logger may not detect the pulses. 
 
The splitter is designed to split digital (on/off) pulses. Ensure that the logging 
systems connected to the splitter have the same current type (AC or DC) coming 
from their Pulse/Digital Input. Do not connect loggers which use the opposite 
current type e.g. do not mix loggers that use AC with those that use DC. 

 

 
Special Conditions 

 
In some extreme conditions, the enclosure of the Pulse-Splitter may be capable 
of generating an electrostatic charge, which could potentially cause ignition. 
When the Pulse-Splitter is being used in a gas meter environment, the device 
shall not be positioned in such a way where external conditions are likely to 
cause an electrostatic charge on the enclosure of the device. In addition, the 
device shall only be cleaned with a damp or conductive cloth. 
 

Disposal 

 
The device must not be disposed of as unsorted waste and must be collected 
separately to ensure correct environmentally sound disposal. Where possible, 
the device should be returned to the manufacturer (or their authorised agent) for 
correct disposal. If this is not possible, your local Waste Disposal Authority 
should be consulted to ensure disposal in compliance with waste electrical and 
electronic equipment (WEEE) regulations that may be in force at the time. 
 

Support and Contact Information 

 
For technical support and queries, please contact: 
 
Enica Ltd 
Unit 7 
Melin Corrwg Business Parc 
Upper Boat 
PONTYPRIDD 
CF37 5BE 
 
Tel: +44 (0)1443 844224 
Fax: +44 (0)1443 381000 
Email: [email protected] 
 

Legal Notice 

 
The information contained in this document is subject to change without notice. 
Enica Ltd makes not warranty of any kind with regards to this document include, 
but not limited to, the implied warranties of sale and fitness for purpose. Enica 
Ltd shall not be liable for errors contained herein or for incidental or 
consequential damages in connection with the use of this document. 