background image

 

 

A

 

base

IOM67 

9  

February 2021 R0 

 

RPM 

AI 

VFD Feedback Speed 

W+/-   AI 

Modulating heating thermostat 

AA1,2   AI 

Ambient / Outside temperature 

DA1,2   AI 

Discharge temperature 

Y+-  

AI 

Modulating cooling thermostat 

HiE 

DI 

High Speed Enable 

ENC 

DI 

Enable Cooling 

OCC 

DI 

Occupied / unoccupied mode 

EnF 

DI 

Enable Fan 

DES 

DI 

Damper end switch 

FbB 

DI 

Air proving switch 

BYP 

DI 

VFD Bypass 

MX1,2  AO 

Maxitrol Modulating Valve 

 

Humidifier Version Terminals 

FV 

DO 

Fill Valve 

MV 

DO 

Mixing Valve 

DV 

DO 

Drain Valve 

FVS 

DO 

Second Fill Valve 

LWP 

CI 

Low Water Probe 

FWP 

CI 

Full Water Probe 

DN1,2  AI 

Drain Water Temperature 

 

CD-XM Terminals 

H N 

 

24Vac Power Supply 

GND 

 

Ground 

LmA,B   

Internal Modbus 

OS 

AI 

Tach 

YS 

AI 

Tachometer - 

GS 

AI 

Tachometer reference 

CB 

AO 

TRIAC output 

120 

 

120Vac input 

SR1,2  DO 

Safety relay 

APPLIANCE TYPES 

DJ STYLE INDIRECT FIRED 

For indirect fired equipment with DJ (E, S, X) style 
burners up to size 140. 

On a call for heating the combustion blower will be 
enabled to full speed to prepurge the heat 
exchanger.  Once the prepurge time has elapsed 
the combustion blower speed will reduce to ignition 
speed and then enable the ignition control to start 
and prove pilot flame, then open the main safety 
valve (SSOV).  After a time delay the pilot valve IS 
disabled.  The burner is allowed to operate from 
low fire to high fire at a 15:1 turndown ratio to 
maintain the requested discharge air temperature 
by modulating the control valve and the 
combustion blower speed.  If heating is not 
required the burner will be disabled and the 
combustion blower will enter a post purge time, 
and then shut down.   

The 

base

 can control either a Maxitrol magnetic 

style modulating valve or an actuator and ball valve 
combination.   

Combustion air blower modulation is controlled by 
either the CD-XM expansion module.  If using an 
electronically commutated motor (ECM) modulation 
is directly controlled from the 

base

DG STYLE INDIRECT FIRED 

For indirect fired equipment, DJX sizes 200 and 
300, and all DG sizes.  These use actuator 
controlled air flow control damper and gas ball 
valves. 

On a call for heating the combustion blower will be 
enabled and the air actuator will open to the 
prepurge setpoint to purge the heat exchanger.  
Once the prepurge time has elapsed the gas and air 
actuators will move to ignition position and then 
enable the ignition control to start and prove pilot 
flame, then open the main safety valve (SSOV). 
Once the pilot flame has proven and the main 
flame is established, the 

base

 will then disable the 

pilot valve.  The burner is allowed to operate from 

Содержание base

Страница 1: ...tion adjustment and operation of this unit Read and understand these instructions thoroughly before attempting installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock carbon monoxide poisoning explosion personal injury or property damage www engineeredair com ...

Страница 2: ... drawings and function sheets provided with the appliance One set is in an envelope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is attached to the control panel door and should never be removed Copyright This document and the information in it are the prop...

Страница 3: ...ted to high voltages Electrical shock could occur if instructions are not followed This equipment contains moving parts that can start unexpectedly Injury or death could occur if instructions are not followed All work must be performed by a qualified technician Always disconnect and lock out power before servicing DO NOT bypass any interlock or safety switches under any circumstances m CAUTION All...

Страница 4: ...MMUNICATION 5 COMPUTER CONNECTION 5 ALARM RESET 6 LED LIGHTS 6 SEVEN SEGMENT DISPLAY 6 CD XM EXPANSION MODULE 8 PRESSURE PORTS 8 TERMINAL DESIGNATIONS 8 APPLIANCE TYPES 9 DJ STYLE INDIRECT FIRED 9 DG STYLE INDIRECT FIRED 9 HE DIRECT FIRED 10 STAGED COOLING 10 SH X HUMIDIFIER 10 ALARMS 11 ...

Страница 5: ...lid state switches Input switching must be mechanical COMMUNICATION Direct connection may be made to a laptop computer using a Cat 5 cable Once connected and correctly configured a web page will appear showing the various operational conditions and settings COMPUTER CONNECTION m Notice The base requires a connection to a computer for detailed information beyond what is indicated on the LED display...

Страница 6: ...ns specific to gas fired heating and mechanical cooling have a number sequence included to describe the current operating mode ALARM RESET Alarms may be reset either from the laptop computer alarm screen or the red reset button near the top left LED LIGHTS Light Description Function Green Power ON Powered OFF No Power to H N Yellow Communication BLINK Comm to CD XM ON Internal Comm OFF Failure Red...

Страница 7: ...A base IOM67 7 February 2021 R0 Standard Version Humidifier Version ...

Страница 8: ...O EC Motor Demand MHW AO Modulating Heating MCW AO Modulating Cooling MEc AO Modulating economizer MPP AO Profile Plate Actuator AL DO Alarm SA DO Supply air DM DO Damper actuator enable CMa DO Relay a Common CMb DO Relay b Common STG1 DO Cooling Stage 1 STG2 DO Cooling Stage 2 STG3 DO Cooling Stage 3 STG4 DO Cooling Stage 4 STG5 DO Cooling Stage 5 HiS DO High Speed Exhaust Fan Start Exl DO Low Sp...

Страница 9: ...en open the main safety valve SSOV After a time delay the pilot valve IS disabled The burner is allowed to operate from low fire to high fire at a 15 1 turndown ratio to maintain the requested discharge air temperature by modulating the control valve and the combustion blower speed If heating is not required the burner will be disabled and the combustion blower will enter a post purge time and the...

Страница 10: ...r a Maxitrol magnetic style modulating valve or an actuator and ball valve combination Variable air volume systems include a burner bypass damper which modulates to maintain the correct burner profile pressure drop STAGED COOLING For staged compressor operation the base will sequence on and off up to 5 compressor stages to attempt to maintain the discharge temperature setpoint As with all staged s...

Страница 11: ...alve feedback has power before the FR and SR contact are energized 81 Gas Valve out of range Gas valve actuator feedback is greater or less than the demand Timed event 86 High Limit High limit safety tripped due to excessively high temperature 87 Flame Relay Wiring Received a gas valve feedback within 500ms of activating the Flame relay output 88 Flame Failure Gas valve feedback has no power after...

Страница 12: ...point during modulation for more than 90 seconds 94 Low Pressure Air flow too low to enable heating 95 Low Pressure Sensor Unable to zero the pressure before the damper has opened 96 Very Low Pressure Occurs if the pressure drops below the very low pressure setpoint after the purge has been completed 97 Far Sensor Flame Failure Occurs if a secondary flame rod is enabled and flame sensing is lost i...