CD-XM EXPANSION MODULE 

A Triac driver slave connected via Modbus 
communication to the 

base

, this module controls 

the combustion motor speed on DJ indirect fired 
heaters.  A 3 wire feedback signal is returned to 
the module to confirm the blower speed.   

 

 

 

 

PRESSURE PORTS 

Marked as H (high side) and L (low side) for use on 
direct fired appliances. 

Pressure ports may not be included on appliances 
that do not require them. 

m

 CAUTION:

   

Do not blow onto the pressure ports.  Excessive 
pressure and moisture will damage it.  The ports are 
fragile and should not be tampered with. 
 

 

TERMINAL DESIGNATIONS

 

Terminals 

indicated

 change on the humidifier 

version. 
 

H N 

 

Power Supply 

GND 

 

Ground 

LmA,B   

Local Modbus 

ECO 

AI 

EC Motor Common 

PWM 

AI 

EC Motor Running Speed 

ECM 

AO 

EC Motor Demand 

MHW  AO 

Modulating Heating 

MCW 

AO 

Modulating Cooling 

MEc 

AO 

Modulating economizer 

MPP 

AO 

Profile Plate Actuator 

AL 

DO 

Alarm  

SA 

DO 

Supply air  

DM 

DO 

Damper actuator enable  

CMa 

DO 

Relay ‘a’ Common 

CMb 

DO 

Relay ‘b’ Common 

STG1  DO 

Cooling Stage 1 

STG2  DO 

Cooling Stage 2 

STG3  DO 

Cooling Stage 3 

STG4  DO 

Cooling Stage 4 

STG5  DO 

Cooling Stage 5 

HiS 

DO 

High Speed Exhaust Fan Start 

Exl 

DO 

Low Speed Exhaust Fan Start 

CMc 

DO 

Relay ‘c’ Common 

MBV 

AO 

Modulating Ball Valve 

MCA 

AO 

Modulating Air Actuator 

FbG 

AI 

Modulating Gas Valve Feedback 

FbA 

AI 

Modulating Air Feedback 

CP 

AI 

Condensate Probe 

PV1,2  DO 

Pilot Valve 

SR1,2  DO 

Safety Relay 

FR1,2  DO 

Flame Relay 

FbV 

DI 

Feedback Gas Valve 

VN 

DI 

Feedback Gas Valve Neutral 

HL 

DI 

High Limit 

EnH 

DI 

Enable Heat 

BFS 

DI 

Blocked Flue Switch 

CAS 

DI 

Combustion Air Switch 

CMd 

DO 

Relay ‘d’ Common 

SDO 

DO 

(HE) Dual Flame Rod 

SDO 

DO 

(DG) Combustion Blower Start 

WPu 

DO 

Water Pump 

FbD 

AI 

Feedback Economizer Damper   

ASP 

AI 

Remote VFD setpoint 

Содержание base

Страница 1: ...tion adjustment and operation of this unit Read and understand these instructions thoroughly before attempting installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock carbon monoxide poisoning explosion personal injury or property damage www engineeredair com ...

Страница 2: ... drawings and function sheets provided with the appliance One set is in an envelope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is attached to the control panel door and should never be removed Copyright This document and the information in it are the prop...

Страница 3: ...ted to high voltages Electrical shock could occur if instructions are not followed This equipment contains moving parts that can start unexpectedly Injury or death could occur if instructions are not followed All work must be performed by a qualified technician Always disconnect and lock out power before servicing DO NOT bypass any interlock or safety switches under any circumstances m CAUTION All...

Страница 4: ...MMUNICATION 5 COMPUTER CONNECTION 5 ALARM RESET 6 LED LIGHTS 6 SEVEN SEGMENT DISPLAY 6 CD XM EXPANSION MODULE 8 PRESSURE PORTS 8 TERMINAL DESIGNATIONS 8 APPLIANCE TYPES 9 DJ STYLE INDIRECT FIRED 9 DG STYLE INDIRECT FIRED 9 HE DIRECT FIRED 10 STAGED COOLING 10 SH X HUMIDIFIER 10 ALARMS 11 ...

Страница 5: ...lid state switches Input switching must be mechanical COMMUNICATION Direct connection may be made to a laptop computer using a Cat 5 cable Once connected and correctly configured a web page will appear showing the various operational conditions and settings COMPUTER CONNECTION m Notice The base requires a connection to a computer for detailed information beyond what is indicated on the LED display...

Страница 6: ...ns specific to gas fired heating and mechanical cooling have a number sequence included to describe the current operating mode ALARM RESET Alarms may be reset either from the laptop computer alarm screen or the red reset button near the top left LED LIGHTS Light Description Function Green Power ON Powered OFF No Power to H N Yellow Communication BLINK Comm to CD XM ON Internal Comm OFF Failure Red...

Страница 7: ...A base IOM67 7 February 2021 R0 Standard Version Humidifier Version ...

Страница 8: ...O EC Motor Demand MHW AO Modulating Heating MCW AO Modulating Cooling MEc AO Modulating economizer MPP AO Profile Plate Actuator AL DO Alarm SA DO Supply air DM DO Damper actuator enable CMa DO Relay a Common CMb DO Relay b Common STG1 DO Cooling Stage 1 STG2 DO Cooling Stage 2 STG3 DO Cooling Stage 3 STG4 DO Cooling Stage 4 STG5 DO Cooling Stage 5 HiS DO High Speed Exhaust Fan Start Exl DO Low Sp...

Страница 9: ...en open the main safety valve SSOV After a time delay the pilot valve IS disabled The burner is allowed to operate from low fire to high fire at a 15 1 turndown ratio to maintain the requested discharge air temperature by modulating the control valve and the combustion blower speed If heating is not required the burner will be disabled and the combustion blower will enter a post purge time and the...

Страница 10: ...r a Maxitrol magnetic style modulating valve or an actuator and ball valve combination Variable air volume systems include a burner bypass damper which modulates to maintain the correct burner profile pressure drop STAGED COOLING For staged compressor operation the base will sequence on and off up to 5 compressor stages to attempt to maintain the discharge temperature setpoint As with all staged s...

Страница 11: ...alve feedback has power before the FR and SR contact are energized 81 Gas Valve out of range Gas valve actuator feedback is greater or less than the demand Timed event 86 High Limit High limit safety tripped due to excessively high temperature 87 Flame Relay Wiring Received a gas valve feedback within 500ms of activating the Flame relay output 88 Flame Failure Gas valve feedback has no power after...

Страница 12: ...point during modulation for more than 90 seconds 94 Low Pressure Air flow too low to enable heating 95 Low Pressure Sensor Unable to zero the pressure before the damper has opened 96 Very Low Pressure Occurs if the pressure drops below the very low pressure setpoint after the purge has been completed 97 Far Sensor Flame Failure Occurs if a secondary flame rod is enabled and flame sensing is lost i...

Отзывы: