DJM2.4 MANUAL
7
Oct 00 R2
IV.
WIRING
Power supply to H and N is 24 VAC and the current draw of the DJM2.4 control itself is 20 VA.
(This
does not include current draw of components attached to it such as burner motors, ignition
controls, gas valves, etc.)
Normally, the DJM2.4 is to be powered from the main control transformer. There are a few rules
concerning input power to the DJM2.4 (Optically isolated power supply).
1.
The voltage powering the main control transformer must come from the same two phases,
which supplies 120 VAC to the combustion motor.
2.
Power to terminals HS must come from the same source that powers terminal H.
3.
Terminals VN (valve neutral) and VFB24 or VFB120 ( valve feedback) must have a pair of wires
coming from the gas valve as per the correct valve voltage.
4.
It is best to keep high voltage wires such as those used on motors and spark ignition separate
from low voltage wires such as used on speed sensors, temperature sensors, flame rod, etc.
This is to avoid “voltage crosstalk”
(stray induced high voltage signals that can adversely affect
electronic controls)
.
V.
SYSTEM TIMINGS
Pre-purge
= 50 seconds
(combustion blower must run 50 seconds before flame can be lit on initial
heat call if no combustion fan is in operation immediately before heat call)
.
Maintained Purge
= 4 minutes
(combustion blower runs after flame is turned off in case there is
another heat call within 4 minutes of the previous calls completion. If heat call occurs while in
maintain purge, the burner can re-light immediately)
.
VI.
POTS
DCAL (Pot 1)
Discharge Calibration
(CW=colder)
BMSZ (Pot 2)
BMS zero.
(CW=reduce)
CONT (Pot 3)
Control type.
(CW=integral; CCW=proportional) (Usual setting for C-TRAC
control is less than 9 o'clock)
SER (Pot 4)
Service pot
(CW=high fire)
IMPORTANT:
When operating in the service mode, the burner will not cycle off.(See
section X.)
SP (Pot 5)
Discharge set point.
(CW=colder)
Adjustment range = 35 to 95°F.
BMSS (Pot 6)
BMS span.
(CW = less gain)
NOTE:
This adjustment is only used when a C-TRAC or other BMS type input signal is
wired to DJM2.4 terminals “+ and -” (including Metasys). (See section XI)