9
TARGET VALUES FOR AIR FLOWS
Target values for air flows in the living areas.
EXTRACT AIR
Kitchen
20
l/s
Bathroom
15 –17
l/s
Toilet
10 –12
l/s
Clothing room
3 –4
l/s
Hobby room
0,7
l/s, m²
Dressing room
2,0
l/s, m²
Washroom
15 –17
l/s
Cleaning cupboard
4,0
l/s, m²
Utility room
15 –17
l/s
SUPPLY AIR
Living room
8 –17 l/s
0,5 l/s, m²
Bedroom
5 –8 l/s
0,7 l/s, m²
Sauna
8 –17 l/s
2,0 l/s, m²
Separate dining recess
0,5 l/s, m²
Hobby room
0,7 l/s, m²
Dressing room
2,0 l/s, m²
KITCHEN VENTILATION
A normal cooker hood is installed over the kitchen stove. The hood should be used only
when cooking. It is still necessary to install an extract vent, connected into the general
ventilation system. The extract air volume should be 20 l/s. The cooker hood should not be
connected to the Fenix ventilation unit.
If needed the cooker hood can be connected to the Fenix ventilation unit exhaust air duct,
for instance in high-rise buildings where it is difficult to install a separate duct for the
cooker hood. Use of separate cooker hood or a combination of a cooker hood and an
extractor is recommended to ensure sufficient suction effect.
Содержание Fenix 120
Страница 12: ...12 Pictures D1 Securing the fastening with two screws...
Страница 13: ...13 Fenix dimension drawing wall mounting left handed...
Страница 15: ...15 Fenix dimension drawing ceiling mounting left handed...
Страница 23: ...23 T E C H N I C A L D A T A CHARACTERISTICS FENIX 60...
Страница 24: ...24 FAN EFFICIENCY RATES FENIX 60...
Страница 25: ...25 CHARACTERISTICS FENIX 85...
Страница 26: ...26 FAN EFFICIENCY RATES FENIX 85...
Страница 27: ...27 CHARACTERISTICS FENIX 120...
Страница 28: ...28 FAN EFFICIENCY RATES FENIX 120...
Страница 30: ...30 W I R I N G D I A G R A M S WIRING DIAGRAM...