Страница 1: ...Solar Inverters INSTALLATION AND OPERATOR S MANUAL...

Страница 2: ...2 REVISION TABLE Document Revision Author Date Change Description 1 0 Falcon Tang 15 05 2012 First release SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS...

Страница 3: ...ersonnel you should know both ac and dc voltage sources are terminated inside this units Each circuit must be individually disconnected before servicing s Read and understand all the instructions cont...

Страница 4: ...ing Earth To avoid risk of electric shock from energy stored in capacitor please wait for at least 5 minutes to access the conductor part of input or output terminals of the inverter after it is disco...

Страница 5: ...C input 13 3 CONTROL PANEL FUNCTIONS 14 3 1 Operate the Function Key 14 3 2 General LCD Display Information 16 4 INVERTER START UP AND OPERATION 17 5 COMMUNICATIONS 18 5 1 Data communications with RS2...

Страница 6: ...1 1 Machine Overview Front View Bottom View Fig 1 Overviews of inverter Control and display panel PV input DC switch optional RS232 outlet RS485 inlet and outlet optional AC terminals cover AC termina...

Страница 7: ...Socket head wrench 1pcs 6 DC socket assembly 1set 2set 3set 7 RS 485 sockets one with 120 ohm terminal resistor 2pcs optional 8 Special RS 232 cable 1pcs 9 Instruction manual 1pcs 10 Monitor software...

Страница 8: ...y damage If the inspection reveals damage to the inverter please call your local supplier or the authorized distributor They will determine if the equipment should be returned for repair They will als...

Страница 9: ...rame as illustrated in the Fig 4 by the screws then hang the inverter on the mounting frame Step3 Fix safety lock screws at upper left side and upper right side as illustrated in Fig 5 with the attach...

Страница 10: ...lock screws The customer is encouraged to perform the following checks Do not install the solar inverter on a gradient surface Check the upper straps of solar inverter and ensure it to fit on to the...

Страница 11: ...6 The PV system diagram A PV Panels Provide DC power to inverter B Solar inverter Converts DC Direct Current power from PV panel s to AC Alternating Current power Because Inverter is grid connected it...

Страница 12: ...three blocks in right hand Connected to AC Grid 2 5 Connecting to the AC Grid Utility A Measure AC grid utility voltage and frequency It should be 230VAC or 220VAC 50Hz or 60Hz and single phase B Ope...

Страница 13: ...th of input wire must be less than 30m By the way generally in the lowest ambient temperature of your installing field the Voc of PV string is the highest B Use the attached connectors for PV array te...

Страница 14: ...he model of inverter for example GI 3000TL C ALARM LED Indicates the fault of inverter D POWER LED Indicates the inverter is running normally E Function Key Used to set different parameter and display...

Страница 15: ...15...

Страница 16: ...em error code Wxx System warning code Auto Test State Auto Testing Protection auto test Program State Programming Update Software Main Operating Messages In LCD STATE DISPLAY CONTENT COMMENTS Normal O...

Страница 17: ...to minimum requirements of the internal controller unit Waiting When the PV string DC voltage is greater than 100V the inverter enters a waiting state and attempts to connect to the grid Normal When P...

Страница 18: ...t DC current sensor fault E14 GFCI failure GFCI Device is damaged 5 COMMUNICATIONS 5 1 Data communication with RS232 Fig 10 RS232 serial port and special RS232 cable Open the cover of RS232 serial por...

Страница 19: ...t is for input ethernet cable with RJ45 connector another socket is for output ethernet cable with RJ45 connector The output ethernet cable reaches the following unit RS485 pin definition is as follow...

Страница 20: ...acant RJ45 socket in the attached accessories When the inverter is not the last one in the chain please draw out the teminal resistor and use it as a vacant RJ45 socket In order to ensure that the com...

Страница 21: ...o normal voltage and frequency variations in AC grid The interface protections ensure that the inverter cease to energize AC grid when any parameters listed as below exceeds the applied operating sett...

Страница 22: ...No grid Check grid connection cables W02 Vin overvoltage Check the Voc of PV string see if it is greater than or too close to max input DC voltage of relative inverter type E01 Isolation error Check t...

Страница 23: ...V 500V Isc pv absolute maximum 14A 14A PV input operating voltage range 100V 450V 100V 500V Max operating PV input current total 11 5A 15A Number of parallel inputs 1 1 Number of MPP trackers 1 1 AC O...

Страница 24: ...24A PV input operating voltage range 100V 500V 100V 500V Max operating PV input current total 20A 23A Number of parallel inputs 2 2 Number of MPP trackers 1 1 AC Output Data Nominal AC output power 3...

Страница 25: ...25 Dimensions W D H in mm 345 162 384 345 162 384 Weight 15Kg 15Kg Operating temperature range 20 C 60 C 20 C 60 C AC grid voltage range and frequency range depend on local standards...

Страница 26: ...put power 4600W 6000W Max continous power 5000W 6000W Nominal Voltage 230Vac 230Vac Nominal Frequency 50Hz 50Hz Max continious current 26A 31 2A Max output overcurrent protection 42A 50A Power factor...

Страница 27: ...27...