The maximum storage times before a freshening charge is required and recommended
open circuit voltage audit intervals are:
ZeMaXXPxx single cells must be given a freshening charge when the cell voltages
approach 2.10V or when the maximum storage time is reached, whichever occurs first.
4.2.6 If the voltage of the individual cells is reduced below 2.02 V, storage damage may have
occurred. Before using such batteries, they should be recharged and tested in a
workshop.