background image

SuperSafe

® 

SBS

® 

EON Technology

® 

batteries are supplied in a 

charged condition, and are capable of extremely high short circuit 

currents. Take care to avoid short-circuiting terminals of opposite 

polarity.

1. Receiving

Upon receipt of a shipment, check that the items delivered
are undamaged and match the carrier’s Bill of Lading.
Report any damage or shortages to the carrier. EnerSys

®

is not responsible for shipment damage or shortages
that the receiver does not report to the carrier.

2. Storage

2.1 Storage Conditions and Time

If a battery cannot be immediately installed it should be
stored in a clean, cool, dry area.
During storage monoblocs and cells lose capacity through 
self-discharge.
High temperature increases the rate of self-discharge and
reduces the storage life. 
The chart below shows the relationship between open-circuit
voltage (OCV) and storage time at various temperatures.

2.2 Refresh Charge

Monoblocs and cells must be given a freshening charge
when the OCV approaches the equivalent of 2.10 Volts per
cell or when the maximum storage time has been reached.
Freshening charge should be by means of constant voltage
charge set between 2.29 and 2.40Vpc with current limit
0.1C

10 

A for 24 hours. Recommended OCV audit intervals are

given in the table below.

2.3 Commissioning Charge

Before conducting a capacity discharge or commencing
cycling, the battery must be given a commissioning charge.
In f oat applications the commissioning charge shall consist
of 7 continuous days of f oat charge at the recommended
f oat voltage (2.29Vpc at 20°C) with no load connected to the
battery. In hybrid applications the commissioning charge
shall consist of 24 hours charge at a voltage equivalent to
2.40 Volts/cell with no load connected.

3. Installation

Whatever your application, 

SuperSafe

 SBS EON Technology

 

blocs and cells can be mounted in any orientation except

 

inverted. However, in cyclic/hybrid applications, EnerSys

 

recommend to install DIN-sized SBS EON Technology 2V

 

cells in horizontal orientation. In such conf

 

guration the

 

instructions below must be complied with.

Do not use terminal posts to lift or handle cells.

Do not install the cells in such a way that the box-lid bond
is resting on a runner.

Always ensure that the arrow on the lid of each unit is
pointing in vertical orientation.

The battery compartment/room must have adequate
ventilation to limit hydrogen accumulation to a maximum of
1% by volume of free air.
Each monobloc/cell is supplied with the terminal/connector
fasteners. 

Instruction Sheet

Temperature

Storage Time

OCV Audit Interval

(°C / °F)

(Months)

(Months)

+10 / +50

48

6

+15 / +59

34

6

+20 / +68

24

4

+25 / +77

17

4

+30 / +86

12

3

+35 / +95

8.5

2

+40 / +104

6

2

2.17
2.16
2.15
2.14
2.13
2.12
2.11
2.10

100
96
91
87
83
79
74
70

O

pe

Ci

rc

ui

t V

ol

ta

ge

 p

er

 C

el

l

A

pp

ro

x. 

%

 S

ta

te

 o

f C

ha

rg

e

Months

0

6

12

18

24

30

36

42

48

+40

°

C +30

°

C

+25

°

C

+20

°

C

+10

°

C

No smoking,

no naked f ames,

no sparks

Electrolyte is corrosive

Electrical hazard

Shield eyes

Clean all acid splash in

eyes or on skin with

plenty of clean water.

Then seek medical help.

Acid on clothing is to be

washed with water

Danger

Read instructions

Warning: Risk of f re,

explosion, or burns.

Do not disassemble, heat

above 60ºC, or incinerate.

Avoid any short circuit.

Metallic parts under voltage on the

battery, do not place tools or items on

top of the battery

Re-cycle

scrap

batteries.

Contains lead

California Proposition 65 Warning – Battery posts,

terminals and related accessories contain lead and lead

compounds, chemicals known to the State of California

to cause cancer and reproductive harm. Wash hands

after handling. 

Отзывы: