3

4.4 Daily Cycle

The battery is normally used with a daily cycle - charge during 

the day hours and discharge during night hours. Typically, the 

daily discharge usage is between 2 and 20% DoD.

4.5 Effect of Temperature on Capacity

If the ambient temperature deviates from 25°C, a correction 

factor must be applied to the published rating in order to 

optimise the service life (see Figure 1 below).

Figure 1

4.6 Operating Temperature Range

The recommended operating temperature range for optimum 

life and performance is between 20°C to 25°C. PowerSafe

®

 

SBS

®

 XC monoblocs/cells can be operated in the temperature 

range -40°C to +50°C. In order to maintain mechanical
integrity of the plastic components, the battery temperature 

in operation should not 50°C. Note, operation of 

batteries at higher temperatures will reduce life expectancy. All 

technical data relates to the rated temperature of +25°C.

4.7 Storage

Monoblocs and cells lose capacity when standing on open-

circuit because of parasitic chemical reactions. The high purity 

of the materials used in the construction of PowerSafe SBS XC 

batteries results in a very low rate of self-discharge, delivering 

up to 2 years shelf life at 20°C before a refresh charge is 

required.
The self-discharge rate of PowerSafe XC monoblocs and cells 

is a function of the temperature.  See below for the rate of self-

discharge at various temperatures:

Temperature 

20°C

25°C

30°C

40°C

Monthly self-discharge 

rate 

1.25% 1.76%  2.5% 

5% 

Batteries should be stored in a cool, dry area. Note that high 

temperature increases the rate of self-discharge and reduces 

storage life. The following table gives the maximum storage 

time before a refresh charge is required and the recommended 

OCV audit intervals, at the given average storage ambient 

temperature:

Temperature

(°C / °F)

Storage Time

(Months)

OCV Audit Interval 

(Months)

+10 / +50

48

12

+15 / +59

34

12

+20 / +68

24

12

+25 / +77

17

6

+30 / +96

12

6

+35 / +95

8.5

3

+40 / +104

6

3

4.8 Refreshing Charge

Blocs and cells must be given a refreshing charge: 

4.8.1

 when the OCV approaches 2.10Vpc, or

4.8.2

 when the maximum storage time is reached, whichever 

occurs first. 
Charge the monoblocs or cells at a constant voltage equivalent 

to 2.40Vpc with minimum 0.1

C10

 Amps current for a period of 24 

hours.

4.9 Installation and Ventilation 

The electrical protective measures and the accommodation 

and ventilation of the battery installation must be carried out in 

accordance with IEC 62485-2, and applicable “local” national 

standards, rules and regulations.
The battery should be installed in a clean, dry area.
Whatever your application, PowerSafe SBS XC batteries can be 

mounted in any orientation except inverted. For the installation 

of cells in the horizontal position, the instructions below must 

be complied with.

•  Do not use terminal posts to lift or handle cells.

•   Ensure that the stand runners are located under the 

container rather than the lid and/or lid/container seal.

•   Always ensure that the arrow on the lid of each unit is 

pointing in vertical orientation.

Effect of Temperature on the 20 hour Discharge Performance

Shown as a Percentage of Normal Capacity @ 25ºC

Temperature (ºC)

% Performance @ 25ºC

140

120

100

80

60

40

20

0

-40               -30               -20               -10                0                  10                20                30                40                50

+        

-

+        

-

+        -