Operation Guide  > PowerSafe

®

 PV Bloc < 

 

7

2.2 Discharging

As a rule, installations will be equipped with a regulator whose voltage threshold values will protect against deep discharge:

Discharge

10h

120h

240h

Low voltage alarm per cell

1.92

1.92V

1.95V

Disconnect voltage per cell

1.80

1.85V

1.90V

2.3 Setting Charging Voltages 

In order to ensure optimum recharge, the following setting charge disconnect and restart voltages can be applied:

Temperature

-20 to 0ºC

0 to 20ºC

20 to 35ºC

> 35ºC

Low recharge-restart voltage 

(Vpc)

2.35V

2.30V

2.30V

2.25V

High recharge-disconnect 

voltage (Vpc)

2.55V

2.45V

2.40V

2.35V

3 MAINTENANCE CHECKS DATA RECORDING

PowerSafe

®

 PV blocs are VRLA batteries and do not have to be topped up.

•  Do not open the valve. Opening could cause lasting damage to the battery and is prohibited.
•  The containers and lids should be kept dry and free from dust. Cleaning must be undertaken with a damped cotton  
 

cloth without additives and without manmade 

fi

 bres or addition of cleaning agents, never use abrasives or solvents.  

 

Avoid electrostatic charging.

•  Every 6 months, check total voltage at battery terminals and battery room temperature.
•  Keep a logbook in which the measured values can be noted as well as time and date of each event like discharge   
 tests 

etc.

Содержание PowerSafe PV Bloc

Страница 1: ...Sustainable solutions PowerSafe PV Bloc Operation Guide for Solar Applications...

Страница 2: ...very corrosive When working with sulphuric acid always wear protective clothing and glasses Exposed metal parts of the battery always carry a voltage and are electrically live risk of short circuits...

Страница 3: ...of Temperature On capacity Correction factors of the capacity according to the temperature are shown in the curve below If the temperature is other than 25 C the correction factors must be applied to...

Страница 4: ...perature range of 20 C to 45 C Humidity 90 The self discharge rate of PV Bloc batteries is a function of the temperature Temperature 25 C 30 C 40 C Monthly self discharge rate 3 4 8 PowerSafe PV Bloc...

Страница 5: ...missioning The initial charge is extremely important as it will condition the battery service life So the battery must be fully recharged to ensure that it is in an optimum state of charge Case 1 Usin...

Страница 6: ...109 121 344 13 5 172 6 8 276 10 9 38 0 83 7 1865 6 62 6 PVB 225 6 195 225 244 9 6 190 10 6 270 10 6 31 0 68 3 2048 3 11 Notes The electrical values shown in the table relate to perfomance from a full...

Страница 7: ...30V 2 25V High recharge disconnect voltage Vpc 2 55V 2 45V 2 40V 2 35V 3 MAINTENANCE CHECKS DATA RECORDING PowerSafe PV blocs are VRLA batteries and do not have to be topped up Do not open the valve O...

Страница 8: ...shall be the best in the industry by being easy to do business with while supplying the highest quality products and services on time and in the most cost effective manner www enersys emea com PV Bloc...

Отзывы: