Operation Guide  > PowerSafe

®

 PV Bloc < 

 

4

Charge Effi ciency

The charge ef

fi

 ciency is the ratio between the quantity of Ah delivered during the discharge and the quantity of Ah 

necessary to restore the initial state of charge.

State of Charge (SOC)

Ah Ef

fi

 ciency

90

> 85

75

> 90

<50

> 95

1 GENERAL OPERATING INSTRUCTIONS 

1.1 Operating Temperature Range

The recommended operating temperature range for PowerSafe

®

 PV Bloc is -15°C to 40°C (Humidity <90%). Optimum 

life and performance is attained at +25°C.
All technical data relates to the rated temperature of +25°C.

1.2 Storage

Store the battery at a dry, clean and preferably cold and frost-free location. Do not expose the cells to direct sunlight.

Limit values for storage conditions: Temperature range of -20°C to +45°C, Humidity <90%

The self-discharge rate of PV Bloc batteries is a function of the temperature.

   Temperature

25°C

30°C

40°C

Monthly self-discharge rate

3%

4%

8%

PowerSafe

®

 PV Bloc has a shelf life of 5 months when stored at 25°C. Higher temperatures increase the rate of self 

discharge and therefore reduce storage life.

This table gives the 

maximum

 storage period before refresh, at the given average storage ambient temperature:

Average storage

 ambient temperature

Maximum storage time

20ºC

6 months

25ºC

5 months

30ºC

4 months

40ºC

2 months

The table hereafter gives an indication of the state of charge of the cells from a reading of the open circuit voltage (OCV). 
PowerSafe

®

 PV Bloc must typically be recharged when they fall to ~75% state of charge.

State of charge

Voltage per cell *

100%

2.13 Vpc

70%

2.09 Vpc

50%

2.06 Vpc

20%

2.02 Vpc

* (Multiply thess voltage by 3 for 6V bloc and by 6 for 12V bloc)

Содержание PowerSafe PV Bloc

Страница 1: ...Sustainable solutions PowerSafe PV Bloc Operation Guide for Solar Applications...

Страница 2: ...very corrosive When working with sulphuric acid always wear protective clothing and glasses Exposed metal parts of the battery always carry a voltage and are electrically live risk of short circuits...

Страница 3: ...of Temperature On capacity Correction factors of the capacity according to the temperature are shown in the curve below If the temperature is other than 25 C the correction factors must be applied to...

Страница 4: ...perature range of 20 C to 45 C Humidity 90 The self discharge rate of PV Bloc batteries is a function of the temperature Temperature 25 C 30 C 40 C Monthly self discharge rate 3 4 8 PowerSafe PV Bloc...

Страница 5: ...missioning The initial charge is extremely important as it will condition the battery service life So the battery must be fully recharged to ensure that it is in an optimum state of charge Case 1 Usin...

Страница 6: ...109 121 344 13 5 172 6 8 276 10 9 38 0 83 7 1865 6 62 6 PVB 225 6 195 225 244 9 6 190 10 6 270 10 6 31 0 68 3 2048 3 11 Notes The electrical values shown in the table relate to perfomance from a full...

Страница 7: ...30V 2 25V High recharge disconnect voltage Vpc 2 55V 2 45V 2 40V 2 35V 3 MAINTENANCE CHECKS DATA RECORDING PowerSafe PV blocs are VRLA batteries and do not have to be topped up Do not open the valve O...

Страница 8: ...shall be the best in the industry by being easy to do business with while supplying the highest quality products and services on time and in the most cost effective manner www enersys emea com PV Bloc...

Отзывы: