2.  Completion of the charging process

When the charger completes the charging process the message 

of 

AVAIL

 will appear.

STOP

 the charger.

After disconnection the battery will be ready for use.

3.  Equalization charge

The start of the equalization charge is indicated by the message 

EQUAL. During the equalization charge, the charger displays 

the current, the battery voltage, voltage per cell, remaining 

time 

4. Faults

Fault

Cause

Solution

DF-CUR

Appears  before  a  DF1  fault  is  dis-

played.

DF1*

Charger problem.

DF1 appears when the charger is not able to supply its output current. 

DF2*

Output default.

Check the correct connection of the battery (reversed polarity cables) 

and the output fuse.

DF3*

Wrong battery.

Too high or too low battery voltage. Battery voltage must be between 

1.6V and 2.4V per cell. Use proper charger for battery.

DF4

Battery discharged more than 80% 

of its capacity.

Charge continues.

DF5

Battery requires inspection. 

DF5  appears  when  the  charging  profile  has  been  achieved  with 

a fault condition, that can be a current increase in regulation phase 

demonstrating a battery heating or a badly programmed regulation  

voltage, or the charging time is too long and has exceeded the 

 

safety  limit.  Check  charging  para  meters:  profile,  temperature,  

capacity, cables. Check the battery (defective cells, high temperature, 

water level..).

DF PUMP

Fault in the air circuit of the electro-

lyte circulation system.

Check the proper operation of the pump via the menu Option-Option 

test. Check the air circuit (pump, tubes). If this fault occurs, the charger 

will adapt the battery charging profile for an  charge.

TH*

Thermal problem in charger resul-

ting in charge interruption.

Verify the proper operation of the fans and/or absence of too high  

ambient temperature, or there is poor natural ventilation to the charger.

WATER LEVEL*

Critical battery electrolyte level.

Top up battery electrolyte. Do not fill in until top of the cell in order to 

avoid overflow by the next charge.

BAT TEMP*

Critical battery temperature.

Wait until the battery temperature cools down, check the battery 

 

state  (water,  profile).  Verify  the  set  up  of  temperature  in  the  menu  

Configuration-Battery-High.  Control  the  temperature  sensor  of  the  

Wi-iQ

®

.

iQ SCAN

Look for present. Wi-iQ

iQ LINK

Set the link. Wi-iQ-charger

MOD TH

Alternating with charge parameters 

- one or more modules in thermal 

fault - the charge process continu-

es - the faulty module(s) is (are)  

dis red led flashing.

Check  that  the  fan(s)  is  (are)  working  correctly  and/or  that  the  

ambient temperature is not too high or whether there is poor 

 

natural ventilation to the charger. 

If all modules are in thermal fault, a TH* fault will follow.

MOD DFC

Alternating with charge parameters 

- one or more module in DF1 fault - 

the charge process continues - the 

faulty module(s) is (are) displayed 

+ red led flashing.

Check power supply. 

If all modules are in DF1 fault, a DF1* fault will follow.

DEF ID

Blocking fault - one or more mo-

dule are not compatible with the  

charger configuration (for example 

24V charger with one 48V module). 

This can happen if the user replaces 

one module with another one with 

a different voltage setting.

Use correct module.

Default of balance voltage detected

by the Wi-iQ

Check  each  battery  cell  during  discharge.  Control  if  the  Wi-iQ  is  

properly adjusted (see Wi-iQ instructions of mounting).

Subject to technical modification without any prior notice. E&OE

www.enersys.com

02.2017

  MESSaGES aND fauLt coDES

(*) A blocking fault preventing charging from continuing.

Please contact EnerSys

®

 Service.