background image

Back to the manufacturer!

Batteries with this sign must be recycled.
Batteries which are not returned for the recycling process must be disposed of as hazardous waste!

When using motive power batteries and chargers, the operator must comply with the current standards, laws,
rules, and regulations in force in the country of use!

The battery charger does not switch on. 

Check if the plug is connected to the supply mains 
and the fuse efficiency.

The charging process does not start, 

Check the connection to the battery and polarity.

‘bat’

message is displayed.

Yellow indicator (4) is not lightning, 

E03 

is displayed. 

Check the battery and its components. 

E01

The charging process is interrupted, maximum 
admissible voltage has been exceeded.

E02

The charging process is interrupted, 
maximum temperature has been exceeded.

E03

The charging process is interrupted, maximum time  
for the charging phase has been exceeded.

SCt

The safety timer has interrupted the charging process. 

Srt

Possible internal short circuit.

FAULT/MESSAGE AND DESCRIPTION

REASON/SOLUTION

www.enersys-emea.com

3

4

5

1

2

Smart battery charger

A = Amps
U = Volts
h = hours
C = Ah
E = KWh

S

6. INFORMATION PLATE

Located on either side of the charger.

7. EC DECLARATION OF CONFORMITY

EnerSys

®

hereby declares that the chargers in the Life On

TM

range covered by this declaration conform to European
Directives:

Directive 2006/95/EC

(Low Voltage Directive): EN60950-1

Directive 2004/108/EC

(ElectroMagnetic Compatibility):

EN61000-6-2, EN61000-6-4:
Immunity and emissions limits for industrial electronics
(class A- Industrial Environments)

Directive 2002/95/EC

(RoHS)

8. FRONT PANEL

CONTROL PANEL

Incorporates 5-digit display (1), selection button (2)
and 3 colors indicators

1.  Five digit display to view 

A - charging current 
U - battery voltage 
h - charging time 
C - charging ampere-hours [Ah] 
E - energy consumption [KWh].

2.  Selection button (S) for the display mode: A, U, h, C, E.

After about 10 seconds of each figure showed, 
the display shows charging current.

3.  Red control button, when it is on, the charging cycle has

started.

4.  Yellow control button, when it is on, the final phase of

the charging cycle has started.

5.  Green control indicator, when  it is on, the charging 

process has finished.

9. OPERATION

Plug the charger into AC socket.

Connect to the battery, check the polarity.

The front panel display will show following information:

• “Hawker” (recognizing the battery)
• Battery voltage
• Charging current
• Charging curve number
• Charging profile: “gel” or “acid”

Please make sure again that the charging profile matches
the battery type.

After connection to the battery the “auto run” test is
initiated automatically.

The battery is ready for charging when the display shows
the battery voltage for approximately 5 seconds.

10. MESSAGES AND FAULT CODES

10.2012 - Subject to revisions without prior notice. E&OE

Отзывы: