background image

AM-HX-IOM AA  December 2018

     3

       

®

For cabinet installations, reference DataSafe

®

 HX Battery Cabinet Systems 

Range Summary (AM-DSCAB-RS).
If provided, intercell connector covers should be installed after completing the 

intercell connections.
Attention: Unless otherwise noted, battery racks and cabinets should not be 

transported with rigid intercell connectors in place.

  Torque

Tighten the M6 connector bolts between 60 to 88 in-lbs (6.8 to 10 N•m). A 

loose connector can cause problems in charger adjustment, erratic battery 

performance, possible damage to the battery and/or personal injury.

4.

 

Cells in Parallel Strings

When utilizing a constant voltage charger, ensure that the connections from 

the charger at the end of each string have the same electrical resistance.
To reduce the risk of current imbalance, the number of parallel strings in any 

system should be limited to six.

5. Charging

  Commissioning Charge

Upon installation, perform a Commissioning Charge on the battery with a 

constant voltage charger by either:

- Charging at 2.40 Vpc at 77°F (25°C) for 24 hours or
- Charging at 2.35 Vpc at 77°F (25°C) for 72 hours.

Follow the Maximum Charging Current values shown in Table 1. After 

completion of the Commissioning Charge at either level, reduce the charger to 

the appropriate Float Charge level for the battery temperature shown in the Float 

Charge Section. A discharge test can be given after float charging for 24 hours. 

  Float Voltage

The float/charge voltage is 2.27 Vpc at 77°F (25°C).
When the average ambient temperature deviates ± 9°F (5°C) or more from the 

reference, it is necessary to adjust the float voltage as follows:

2.33 to 2.36 Vpc at 32°F (0°C)
2.30 to 2.33 Vpc at 50°F (10°C)
2.27 to 2.30 Vpc at 68°F (20°C)
2.25 to 2.28 Vpc at 77°F (25°C) (reference) 
2.23 to 2.26 Vpc at 86°F (30°C)
2.22 to 2.25 Vpc at 95°F (35°C)

  Equalize Charge

The battery can be charged at an elevated voltage of 2.40 Vpc (14.4 Volts 

for the battery) for the purpose of an equalize charge or as part of a 2-step 

recharge profile to reduce charge time. Charge time at 2.40V should not 

exceed 16 hours and the current limits in Table 1 must be followed. 

  Ripple Current

Unacceptable levels of ripple current from the charger or the load can cause 

permanent damage and a reduction in service life. It is recommended to limit 

the continuous ripple current to the values of the Table 1 (in amperes).

Table 1

  Charging Current

The recommended charging method for DataSafe HX batteries is current 

limited, constant voltage charging. Refer to Table 1 for the current limits for 

each battery model.

  State of Charge

The battery state of charge can be determined approximately by measuring 

the open circuit voltage after the battery has been at rest for a minimum of 24 

hours at 77°F (25°C). See Table 2. 

Table 2

State of Charge

Voltage per Cell

Voltage per Battery

100%

2.12 to 2.14

12.72 to 12.84

80%

2.09 to 2.11

12.54 to 12.66

60%

2.05 to 2.08

12.30 to 12.48

40%

2.01 to 2.04

12.06 to 12.24

20%

1.97 to 2.00

11.82 to 12.00

6. Discharging

  End of Discharge Voltage

The end of discharge voltage must be limited to a minimum value of 1.60 Vpc.
A protecting system shall have to be installed to prevent deep discharge.

  

Discharged Cells

DataSafe HX batteries must not be left in a discharged condition after 

supplying the load, but must be immediately returned to float recharge mode.
Failure to observe these conditions may result in greatly reduced service life 

and unreliability.

  

 Accidental Deep Discharge

When the battery is completely discharged, the sulfuric acid is completely 

absorbed and the remaining electrolyte consists only of water.
At this point, the sulfation of the plates is at its maximum, considerably 

increasing the cell’s internal resistance. 
Important notice: This type of deep discharge will provoke a premature 

deterioration of the battery and a noticeable effect on life expectancy.

For temperature correction factors for use when load testing a battery, 

please refer to the Temperature Correction factor tables published in 

IEEE Standard 1188, latest version.

7.

 

Maintenance and Records

DataSafe HX batteries are virtually maintenance-free, sealed, lead acid 

batteries and need no water addition. These batteries are equipped with self-

resealing, flame-arresting safety vents.
The containers and lids shall be kept dry and free from dust. Cleaning must 

be done with a cotton cloth dampened with water only. Check monthly that 

total voltage at battery terminals, while on float, is (N x 2.25 to 2.28 Vpc) for a 

temperature of 77°F (25°C), (where N is the number of cells in the battery). 
Every 12 months, read and record the following:

  Individual battery voltages (in volts)

  Cell-to-cell connection resistance (in ohms)

  Terminal connection resistance (in ohms)

  Ambient temperature in the immediate battery environment

Keep a logbook to record values, power outages, discharge tests, etc.
An autonomy check can be carried out once or twice a year.
The above record taking is the absolute minimum to protect the warranty. This 

data will be required for any warranty claim made on the battery.

 Battery Model

Maximum 

Charging Current 

(Amps)

Maximum Allowable  

Ripple Current  

(Amps RMS)

12HX205-FR

11.0

2.1

12HX300-FR

18.0

3.5

12HX330-FR

21.0

4.1

12HX400-FR

24.0

4.7

12HX505-FR

30.0

5.9

12HX540-FR

31.0

6.1

Отзывы: