15
0120011-J0 Rev M
4� Features
4�1 Converter Modules
A module contains four isolated DC to DC converters with a common control and supervisory circuit. Each module
output operates independently. An internal micro controller monitors both the inputs and outputs of the converters,
turns the converters on and off, and generates a converter fail alarm if required.
4�1�1 Status Indicators
The converter module has four LED indicators – one per converter. The LEDs are color-coded to indicate converter
status as follows:
Table A — Converter Status LEDs
LED State
Converter Status
Green
Normal
Blinking Green
Remote shutdown enabled on individual
channel/converter
Blinking Green
(All 4 LEDs)
Shelf is not compatible with the module
Module not seated properly
Yellow (All 4 LEDs)
Recoverable:
• Ambient temperature high
Blinking Yellow (All 4
LEDs)
Input qualify not OK
Blinking Yellow
Recoverable:
• OCP/Overload
Non-recoverable:
• Converter Input Fuse fail
Red
Locked-State:
• OVP
Non-recoverable:
• Converter Output Fuse fail
Blinking Red
Recoverable:
• GFI
OFF (All 4 LEDs)
Recoverable:
• No power
Non-recoverable:
• Main Input Fuse cut-off
Chasing Red/Green
Pattern (All 4 LEDs)
Locate feature enabled
4�1�2 Converter Alarms
Two converter fail outputs are present at the card edge connector. Alarms are activated after a one second delay for
the following conditions:
•
Internal regulation fails
•
Output voltage <±140V
•
Over Voltage Protection (OVP) operation
•
Ground Fault Interrupt (GFI) trip
•
Input fuse or output fuse fail
•
Output short circuit (±30V ± 20%)
•
Input voltage out of range
•
Heatsink/ ambient temperature out of range (Over Temperature Protection - OTP)
4 Status LEDs–
one per converter
Содержание alpha LPS36
Страница 1: ...LPS36 Line Power System Technical Guide 0120011 J0 Effective 07 2020...
Страница 2: ......
Страница 4: ......
Страница 85: ......