0170022-J0 Rev A
Page 82
To add and configure battery temperature sensors:
1. Go to
System > FXM System > Inventory > Battery > Battery String
. On the
Temperatures
table, click the
Add Temperature Value
button. The table will be populated with a new line for
temperature value.
2. Click the more details icon on the right-side of the line for the new temperature value.
3. A new page displays with information about the new temperature value. In the
Configuration
table you can enter an optional name and description if desired.
4. It is mandatory to select a
Battery Temperature Source
for the temperature value. Click the
more details icon and select the desired temperature input. The drop-down list displays all avail
-
able temperature inputs. The FXM HP has one temperature probe, used for battery temperature,
from the FXM ADIO module.
5. In the
Status
table, verify that the temperature is now reading a temperature value.
6. Repeat these steps for each temperature value required. When finished navigate back to the
Battery
page.
9.3.6
In the
Temperatures
table on the
Battery
page, you should now see a list of temperature values.
The battery
Status
table should show the minimum, average and maximum temperature values as
determined from the list of temperatures. The system battery temperature should now show a valid
reading for battery temperature.
Configure the Charging System Function
You can enable/disable and set the charging voltage in the absorption charging state. If you disable
Elevated Absorption Charging or the arming threshold was not reached, then the absorption charging
stage will be done at the float voltage. You can configure
Elevated Absorption Charging
to
terminate on a timeout and a low current threshold.
Absorption charging, at an increased voltage, is normally done for deep discharges only so there is an
Absorption Arming Threshold
. A battery discharge must reach a voltage below the
Absorption
Arming Threshold
for
Elevated Absorption Charging
to be activated on the recharge.
To configure the Charging System:
1. Go to
System > FXM System > System Functions > Charging
.
2. In the
Primary Charge Current Control
table, click on
Turn Off Charger
button to turn off the
charger.
3. Click on
Turn on Charger at Maximum Current
to set the Nominal Charging current limit.
4. To set the current limit to a specific value, set the
Charge Current Limit
to an appropriate value.
See your battery manufacturers’ data sheet for charging recommendations.
5. Confirm the value of
Charge Current Limit Amps
is correct.
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......