0170022-J0 Rev A
Page 64
Figure 54:
Three-Stage Charging Cycle
Bulk Charging
After the bulk charging stage, the battery should be in a 70%-90% state of charge. In the
Bulk
Charging
, the charging current is limited to the Charge Current Limit setting.
Absorption Charging
After the absorption charging stage, the battery should be in a 95%-98% state of charge. In the
Absorp
-
tion Charging
menu, you have the option to charge the battery at a voltage higher than the float
voltage. The higher voltage is used to speed up the absorption charging stage after a prolonged AC
power failure.
Float Charging
The float charging stage brings the batteries to 100% state of charge and maintains it there. When the
system is in the float stage it is usually at the
Float Voltage
.
9.2.3
Battery Temperature Compensation
Temperature Compensation (Temp Comp) is used to prolong battery life and help prevent thermal
runaway. When battery temperature compensation is enabled, the controller uses the battery tempera
-
ture to calculate an offset which is applied to the battery voltage.
A typical temperature compensation curve for a 48V battery system is shown in the following figure.
Battery Voltage
Charge Current
Stage 1
Bulk Charge
Rising Voltage
High Constant Current
Stage 2
Absorption Charge
Constant Voltage
Declining Current
Stage 3
Conditioning
Constant Voltage
Low Current
Current (A)
V
oltage (V)
Time (hrs)
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......