0170022-J0 Rev A
Page 19
6
Installation
6.1
Installation
WARNING
:
The Alpha FXM HP module MUST be correctly grounded for proper operation.
The input and output lines to and from the Alpha FXM HP MUST have disconnect devices attached.
This system is designed to be installed in a restricted area accessible by qualified service personnel.
Once the installation location has been planned and prepared, you are ready to install the Alpha FXM
HP. There are three steps to setting up the Alpha FXM HP:
1. Mounting the Alpha FXM HP
2. Wiring the external battery
3. Wiring the Alpha FXM HP
6.1.1
Tools Required
Various tools are essential for product installation. Insulated tools are recommended. Use this list as a
guide:
•
AC/DC voltmeter
•
Labels or masking tape and marker
•
Torque wrench for input/output terminal blocks
•
Slot head screwdriver to fit the terminal blocks
•
Minimum #10 AWG copper wire for input/output terminal blocks
•
High strength, flame-proof tape
•
Battery terminal corrosion inhibitor such as NOCO Company NCP-2 or Sanchem Inc. No-Ox ID
Grease “A”
6.2
Mounting the Alpha FXM HP
The Alpha FXM HP can be placed on a shelf with no other parts needed. It can also be rack or wall
mounted or secured to a shelf, such as on an outdoor enclosure shelf, with the optional mounting
brackets, as shown in the figure below. The brackets and screw kit is available from Alpha Technolo
-
gies.
Table 8:
FXM HP Part Numbers (Sheet 1 of 2
Product
Part Number
FXM HP650-24, 120V
0170023-002
FXM HP650-24, 230V
0170023-201
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......