0170022-J0 Rev A
Page 8
3.1
FXM HP - AVR Transition
Compliance
Safety
UL 1778, CAN/CSA-C22.2 No. 107.3-14, EN 62040-1
EMC
FCC CFR47 Part 15, Class A, CSPR22, EN62040-2, EN55022 Level A, C62.41
1. Measured at nominal input voltage and load.
2. Measured at nominal AC Input and full load.
3. Measured at nominal DC Input and full load.
4. Derates 1.4% per °C past this range until a maximum of 74°C.
5. Derates 2°C per 300m (1000ft) above 1400m (4500ft).
6. Measured at 25°C ambient temperature.
Table 1:
Specifications: FXM HP 650, 1100, 2000 (Continued) (Sheet 4 of 4)
FXM HP
650-24
120Vac
FXM HP
650-24
230Vac
FXM HP
650-48
120Vac
FXM HP
1100
120Vac
FXM HP
1100
230Vac
FXM HP
2000
120Vac
FXM HP
2000
230Vac
Table 2:
AVR Transition: FXM HP 2000 - 120V
AVR Transition
FXM HP 2000-120 120V (Vac)
Inverter to Boost 2
89.4
Boost 2 to Boost 1
99.5
Boost 1 to Line
112.7
Line to Buck 1
129.6
Buck 1 to Inverter
148.4
Inverter to Buck 1
141.5
Buck 1 to Line
126.4
Line to Boost 1
110.4
Boost 1 to Boost 2
96
Boost 2 to Inverter
84.8
Vin (Vac) all thresholds are /-0.5V of the specified values
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......