0170022-J0 Rev A
Page 108
Data capture can either be started and run continuously or an equation can be used to control data
capture.
Datalogs are saved to the file system when the controller is reset by a user, as well as being automati
-
cally saved once every day. If power is lost to the controller, there is potential for some data loss.
Figure 62:
Datalog Window: Status, Signals, Configuration and Preview Chart
If any
Data Signals
are not configured, a
Datalog
will not start.
If there is a
Clock Error Alarm
—which means that the date has not been set, a
Datalog
will not start.
If a
Datalog
is running and a controller reset occurs, the
Datalog
will try to resume data collection on
controller startup.
If there is data available, a
Preview Chart
displays up to 30 samples. If there are more than five
Data
Signals
, only the first five signals are displayed in the preview. If a value is unknown, it is displayed on
the preview as a zero value.
Create a Datalog
There are three stages to setting up a
Datalog
:
•
Add a
Datalog
•
Add the
Data Signals
•
Run the
Start Capture
command