79
704-939-B10-001 Rev. A5 (06/2019)
8.0 Battery Sense Wire Kits
8.1 36V Single and Dual Strings
Battery Sense Wire Kits are required to power the transponder, as well as for individual battery voltage monitoring. The
Battery Sense Wire Kits are connected to the transponder battery connections A/B for battery strings 1 and 2 and the C/D
connector for battery strings 3 and 4.
3B
2B
1B
3A
POS
NEG
2A
POS
NEG
1A
POS
NEG
POS
NEG
POS
NEG
POS
NEG
R E D (+)
B L A C K (-)
A/B [C/D] NEG
Pin 1
Vbatt 3A
[C] 36V
Pin 4
Vbatt 3B [D] 36V
Pin 7
Vbatt 2B [D] 24V
Pin 6
Vbatt 1B [D] 12V
Pin 5
Vbatt 2A
[C] 24V
Pin 3
Vbatt 1A
[C] 12V
Pin 2
1
2
3
4
5
6
7
8
3A
POS
NEG
2A
POS
NEG
1A
POS
NEG
R E D (+)
B L A C K (-)
A/B [C/D] NEG
Pin 1
Vbatt 3A
[C] 36V
Pin 4
Vbatt 2A
[C] 24V
Pin 3
Vbatt 1A
[C] 12V
Pin 2
1
2
3
4
5
6
7
8
Sense Wire Kits:
Alpha P/N: 874-842-20 (6')
Alpha P/N: 874-842-28 (9')
Sense Wire Kits:
Alpha P/N: 874-842-21 (6')
Alpha P/N: 874-842-27 (9')
Fig. 8-1, 36V System, Single String
Fig. 8-2, 36V System, Dual String