7.3 Power Factor:
Meter display Power factor along with load type indication. Meter
is capable to display both total as well as phase wise power factor
PF consists of 2 things, one is magnitude and second one is load
type. for example if meter is showing 0.855L that means PF
magnitude is 0.855 and load type is inductive. Below are some
sample screens.
At RS485 port, PF will be shown as below:
if PF IS
0.894L
(Inductive load) then at port we get
0.894
if PF IS
0.894C
(Capacitive load) then at port we get
-0.894
7.4 Ampere
: Meter can display average as well as phase wise ampere. Average
ampere is given by
in case of star and delta, I
avg
= IR + IY + IB
3
In case of single phase, I
avg
= IR
LCD
LCD
LCD
Series
Series
Series
ENERSOL
ENERSOL
ENERSOL
MFLR09
MFLR09
MFLR09
PROG
PROG
PROG
COM
COM
COM
Tot: 0.855L PF
PF: r0.855L
Amp: r5.000
0002504.3KWh
LCD
Series
ENERSOL
MFLR09
PROG
COM
Avg: 4.978 Amp
0002504.3KWh
y0.869C b0.954L
y4.978 b4.785
Row 1
: Total PF. Display
reads as total PF is 0.855
and load type inductive.
Row 2:
Total KWh. Display
Reads as 2504.3 Kwh or
2504.3 units of active energy.
Row 1
: Average Ampere. Display
reads as avg. ampere is 4.978
Row 2:
Total KWh. Display
Reads as 2504.3 Kwh or
2504.3 units of active energy.
Row 1:
Phase wise PF . Display
reads as
R Phase PF = 0.855 (Inductive Load)
Row 2:
Display read as
Y Phase PF = 0.869 (Capacitive Load)
B Phase PF = 0.954 (Inductive Load)
Row 1:
Phase wise Amp . Display
reads as
R Phase Amp = 5.000
Row 2:
Display read as
Y Phase Amp = 4.978
B Phase Amp = 4.785
Содержание MFLR09