INSTALLATION INSTRUCTIONS
SPECIFICATIONS
DESCRIPTION
3
WARNING
Turn the POWER OFF at the circuit breaker before installing the
sensor
Read and understand these instructions before installing. This device
is intended for installation in accordance with the National Electric Code
and local regulations. It is recommended that a qualified electrician
perform
s
this installation. Make sure to turn off the circuit breaker or
fuse(s) and make sure power is off before wiring the device.
Use copper wires only.
WIRING DIRECTIONS
As illustrated in Figure 1, The DWOS-
J
has a 180° detection range with a
maximum distance of 40’ detection in front of the sensor
and 20' on the sides
.
For maximum results, the sensor must be properly installed between the height
of 4’ to 5’ and away from obstructions such as walls, furniture and transparent
barriers like Low-E glass.
The DWOS-
J
uses advanced passive infrared sensor to detect heat emitted
motion. The sensor switch can turn on a load and keep it on as long as it
detects motion. The sensor will automatically shut off the load at the end of the
selected time delay. The countdown of the selected time delay starts after the
last motion detected. The sensor is customizable with dials that can adjust
Time
Delay
, detection
Range
, ambient
Light Level
, and
a switch to change between
Occupancy/ Vacancy
mode
s
.
1.
Connect RED wire from sensor to the LOAD wire.
2.
Connect BLACK wire from sensor to the HOT wire.
3. Connect GREEN wire from sensor to the GROUND
wire.
ADJUSTMENT
DWOS-
J
OCCUPANCY / VACANCY (2-IN-1)
SENSOR SWITCH
Incandescent .......................................................................… 800W
Time Delay..........................................................…… 15Sec to 30Mins
Light Level.................................................................... 30 Lux--Daylight
Fluorescent
/
Ballast......................800VA@120VAC /1600VA@277VAC
Operation Temperature...................................................... 32 F--131 F
Voltage .................................................................... 120/277VAC,60Hz
Motor ...................................................................................…… 1/4Hp
COVERAGE
Figure 1
Max. 20'
on the sides
Max. 40'
from front
Installation
Height: 4' - 5'
Detection Range
Wiring Diagram
Neutral
White
Hot
Black
Ground
Green
Load
Red
Load
The control panel cover is also the push button on the switch.
Remove the
push-button
cover plate
by prying from the bottom of the
push-
button and
pulling outward.
Time dial
This dial adjusts the time delay. Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)
Range dial
This dial adjusts the detection range.
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4).
Note: Use the greater setting for larger coverage area
.
Control Panel Cover
LED Indicator
AUTO OCC VAC
TIME
TEST
Min
5
20
Min
30
Min
RANGE
3
2
Mounting Yoke
Fresnel Lens
AUTO OCC VAC
4
1
(Push-button)
Figure 4
10 Min
Ambient Light Level Adjustment
To adjust
the Ambient
Light Level, make sure that power has been
restored to the switch for at least 3 minutes.
The Ambient Light Level
must be adjusted ONLY when the desire level of ambient light in the
room is reached.
•
Set the Mode switch to VAC.
•
Hold down the Manual ON/OFF push button until the Load comes on
(about 6 seconds). Once the Load comes on, release the button within
4 seconds. The Load will turn off for about 10 seconds, then the Load
will turn on for about 2 seconds and off again.
•
To save, set the Mode switch to AUTO or OCC.
The sensor will ONLY activate when the level of ambient light in the room is
reached or below the programmed light level and motion is detected.
To
reset the Ambient light level back to Factory Default (Daylight):
•
Hold down the Manual ON/OFF push button until the Load comes on
(about 6 seconds).
•
Continue holding the button until the Load turns off (about 5 seconds),
then release.
•
To save, set the Mode switch to AUTO or OCC.
The sensor is now restored back to Factory Default and will activate when
motion is detected regardless of ambient light level.
Figure
2
Figure
3