INSTALLATION INSTRUCTIONS

AND USER GUIDE

V

ENMAR

 

MODELS

B

ROAN

 

MODELS

EVO5 700 HRV HEPA

EVO5 500 HRV

HRV 7.1 HEPA

HRV 5.1

* These products earned the ENERGY STAR

®

 by meeting strict energy efficiency guidelines set by Natural Resources   

  Canada and the US EPA. They meet ENERGY STAR requirements only when used in Canada.

R

ESIDENTIAL

 

INDOOR

 

USE

 

ONLY

READ AND SAVE THESE INSTRUCTIONS

20846 rev. 02

VB0186

VB0187

VB0068

VB0067

Содержание EVO5 500 HRV

Страница 1: ...HEPA HRV 5 1 These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Ca...

Страница 2: ...ugged into a mating 3 prong grounding receptacle grounded in accordance with the national electrical code and local codes and ordinances Do not remove the ground prong Do not use an extension cord 8 D...

Страница 3: ...RTS 11 3 7 INSTALLING DUAL EXTERIOR HOOD 11 12 3 7 1 ASSEMBLING DUAL EXTERIOR HOOD 11 3 7 2 LOCATING DUAL EXTERIOR HOOD 11 3 7 3 CONNECTING TANDEM TRANSITION TO DUAL EXTERIOR HOOD 12 3 8 CONNECTING TH...

Страница 4: ...evel Homes with more than one level require at least one exhaust register at the highest level See figure at right 1 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM VH0089 Stale air coming from...

Страница 5: ...SITION VD0118A 8 222 mm 9 248 mm The joist opening needed to install theTandem tansition included in ISKV1000 and ISKB1000 installation kits must be 9 248 mm minimum Also the maximumheightoftheTandemt...

Страница 6: ...nstall the door NOTE On EVO5 700 HRV HEPA and HRV 7 1 HEPA units only write the installation date on the HEPA filter frame for future reference see illustration at right TO P DES SU S FR O N T AV A N...

Страница 7: ...minimum Do not ventilate crawl spaces or cold rooms Do not attempt to recover the exhaust air from a dryer or a range hood This would cause clogging of the filters and recovery module If the house ha...

Страница 8: ...level to ensure the greatest possible air circulation Keep in mind that the fresh air diffuser must be located as far as possible from the stale air diffuser If desired you can install another diffuse...

Страница 9: ...orresponding port then do the same for the exhaust air to building duct and port See illustration at right NOTE Use an insulated duct not included if the duct will have to go through a space where it...

Страница 10: ...will need two exterior hoods instead of one In this case do not use the Tandem transition go to point 3 6 2 and refer to the optional single hood enclosed instructions For each duct pull back the ins...

Страница 11: ...around the joint Compressed insulation loses its insulation properties and causes water dripping due to condensation on the exterior surface of the duct CAUTION 3 7 INSTALLING DUAL EXTERIOR HOOD Exte...

Страница 12: ...de duct will be located on top CAUTION VD0085 XMAS TREE PIN Join the end of the Tandem transition to the rear of the exterior backplate Secure with 2 Xmas tree pins and seal properly with duct tape Th...

Страница 13: ...of the LED will show on which defrost cycle the unit is set NOTE No command will be taken until the unit is fully booted 4 2 DEFROST CYCLES Five seconds after the booting sequence is done the LED 2 wi...

Страница 14: ...tic operation of the unit and or the wall control Never install more than one main wall control per ventilation unit Keep control low voltage wiring at least 1 foot 305 mm away from motors lighting ba...

Страница 15: ...artment interface Plug the unit Usetheterminalconnectorincludedintheinstallationkittoperformtheelectricalconnection for main and optional wall controls Check if all wires are correctly inserted in the...

Страница 16: ...ee operation modes for more details ECO mode key 4 6 1 OPERATION MODES 4 6 MAIN WALL CONTROL USE When the wall control is ON press the MODE key to choose the operation mode of the ventilation unit Ope...

Страница 17: ...When the wall control is ON press the ECO key to access directly to ECO mode without scrolling all other modes on the screen Press another time to exit the ECO mode and return to the previous operati...

Страница 18: ...AYED TEMPERATURE UNIT NOTE Prior to perform this setting the wall control must be ON Press and hold on ECO key during 4 seconds NOTE To get back to C for temperature display repeat the complete proced...

Страница 19: ...appear on screen while 25 13 will flash factory set value OR according to the displayed temperature unit chosen To enter a lower value press on ECO key to enter a higher value press the TURBO key OR 4...

Страница 20: ...ances When the wrench icon appears on wall control screen perform the required maintenance according to the unit model MAINTENANCE TABLE FOR EVO5 500 HRV AND HRV 5 1 UNITS APPEARANCE MAINTENANCE TYPE...

Страница 21: ...wall of the unit with a damp cloth then wipe with a dry one Remove dust on core using a vacuum cleaner with a soft brush attachment Wash both core filters under hot water with mild soap Rinse thoroug...

Страница 22: ...water and mild soap dishwashing liquid Rinse carefully drain off water and reinstall with its filters For EVO5 700 HRV HEPA and HRV 7 1 HEPA units only The heat recovery core must be reinstalled BEFO...

Страница 23: ...the unit in AUTO or ECO mode See Control section 4 6 1 Operation modes on pages 15 and 16 Change the defrost cycle of the unit to PLUS See 4 2 Defrost Cycles on page 13 6 The LED of the integrated def...

Страница 24: ...ch unit and are manufactured to comply with all the applicable certification standards and maintain a high standard of safety Any third party replacement part used may cause serious damage and drastic...