The sensor shall be install as close as possible to the inlet and outlet port of the tank
and insulate well.
After install temperature sensor, the sensor wiring shall go through the pipe to get into
the house
,
and then connect with temperature monitor. The monitor shall be installed
in a place where can be monitored expediently and keep it dry.
The recommended temperature monitor SmartMaxx-DHWV2 can be installed
expediently, and you just need fix the monitor onto the wall and insert the thermal
sensor connector into the sensor jack of the monitor. You can refer the monitor
diagram below.
To determine whether the solar system is working, observe the thermometer when the hot
water is being used in the house. The water returning from the collector on a sunny day
should be at least 10 Fahrenheit warmer than the water going up to the collector. The
temperature of the cold water and hot water is displayed on the monitor.
The monitor main unit shall work normally under the ambient temperature between -
10 and 60°C, the humidity under <90%RH. The thermal sensor shall meet the
working temperature between -40-110°C. The recommended measure accuracy is
0.1°C.
If the solar water heater is installed either on a metal roof or in a trafficable area, such
as on an accessible roof, then the solar hot and solar cold pipes must be insulated. The
solar hot and solar cold pipes may be required to be insulated to comply with local
regulations.