![Energie FF Evi 10 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/energie/ff-evi-10/ff-evi-10_installation-and-instruction-manual_2409982037.webp)
ENERGIE
Page | 35
17.14
Installation of remote controller
To install the remote terminal, no
configuration is required on the µC²SE, as
the terminal works with any serial address
set for parameter H10.Check, however,
that is fitted with the serial interface the
UC2SE FCSER00000. When firsts witched on the display will show the
firmware version of t he UC2SE
After around 4s the main screen will be
displayed, with the symbols that represent
the status of the µC²SE.
In the event where the RS485 connection
is not performed correctly or the controller
is off, the terminal will clear the display and
show the message “OFFLINE”.
Pressing the “Up”+“Down”+“Sel” buttons
together for more than 6 seconds displays
the “INFO” screen containing information on
the UC2 system and on the communication
.Pressing the “Prg” button returns to the
main screen.
Insert 120 ohm terminal
resistor between Tx/ Rx+
and Tx/ Rx- for lines longer
than 20 m.
Max . length = 250m
( mi n. cross - section
1,5mm²/AWG16)
Fuse 250 mA
24 Vac /17VA
Telephone cable
Max . length 40m
R
J1
2
Po
w
er
su
pp
ly
Содержание FF Evi 10
Страница 13: ...ENERGIE Page 11 1 11 1 D Di im me en ns si io on n 11 1 Model FF Evi 10 11 2 Model FF Evi 15 and FF Evi 17...
Страница 50: ...ENERGIE Page 48 21 4 Central heating cooling and DHW 21 5 DHW...
Страница 52: ...ENERGIE Page 50...
Страница 53: ...ENERGIE Page 51...
Страница 54: ...ENERGIE Page 52...