[0203072TSS] TSS-D Battery Chargers r1
User's Manual
3. INSTALLATION OF THE CHARGER
Conditions of use:
•
Operating temperature:
5°C to 45°C
•
Storage temperature:
-20°C to 60°C
•
Relative humidity:
less than 75%
__________________________________________________________________________________________________________________________________________________
Page 5/19
CAUTION!
Risk of electrical shock!
The charger can be installed by qualified personnel only.
To prevent fire or shock hazard, do not expose the unit to rain or moisture.
Don't use the unit in presence of flammable gas, because it can generate sparks.
ATTENTION!
Make sure that the unit's maximum input power (reported on the data label) is available from
your power supply, and verify that the unit's operating voltage is correct.
Allow adequate air circulation to prevent internal heat buildup.
Don't place the unit near heat sources such as radiators or air ducts, or in a place subject to
direct sunlight, excessive dust, mechanical vibration or shock.
ATTENTION!
The proper setting of the power transformer taps is fundamental
for the correct operation of the charger.
If the real AC input voltage is different than the AC nominal voltage to which the charger is set,
the charging current of the charger may be significantly different than the nominal.
NOTE
The BOARD FOR INPUT VOLTAGE SELECTION is present only in chargers with
3x 208 / 240 / 480 Vac input, and it's NOT present in chargers with 3x600 Vac input.
The PLUGS FOR INPUT VOLTAGE ADJUSTMENT are present in all the chargers.